13.2 Setting Parameters for Grid Management Services in
the Inverters
To enable the inverters in the system to implement the grid management service setpoints of the
Cluster Controller, you will first need to set the corresponding parameters in the inverters.
Requirement:
☐ You must have received a personal SMA Grid Guard code (application form for the
SMA Grid Guard code available at www.SMA-Solar.com, for further information on the
SMA Grid Guard code, see Section 15.5, page 83).
Procedure:
1. Log in to the Cluster Controller as
Installer
.
2. Select the SMA Grid Guard symbol (
) in the status bar.
☑ This opens the SMA Grid Guard dialog.
3. In the field
Individual access code
, enter the personal SMA Grid Guard code.
4. Select [
OK
].
☑ The SMA Grid Guard mode is activated. In the system tree, updating the symbols for
access rights (SMA Grid Guard symbol and padlock symbol) can take up to two minutes.
5. Select the system in the system tree and select the menu
Settings
in the device menu.
6. Select the parameter group
System & device control
.
7. Select [
Edit
].
8. To enable the inverters to receive and implement setpoints for active power limitation from the
Cluster Controller, proceed as follows:
• Select the group
Configuration of feed-in management
.
• In the dropdown list
Operating mode Active power
, select
Act. power lim. via PV
system ctrl
.
9. To enable the inverters to receive and implement setpoints for reactive power from the
Cluster Controller, proceed as follows:
• Select the group
Conf. of the static voltage maint. at Q on demand
.
• Select the desired entry in the dropdown list
Operating mode of static voltage
stabilisation
.
Setting
Explanation
cosPhi, specified by PV system
control
The inverter only implements
cos Phi
setpoints.
Q specified by PV system control
The inverter only implements
Reactive power in %
setpoints.
cos Phi or Q specification through
optimum PV system control
The inverter implements
cos Phi
setpoints as well as
Reactive power in percent
setpoints.
10. Select [
Save
].
13 Grid Management Services
SMA Solar Technology AG
User Manual
63
ClusterController-BA-en-15