![SMA CLCON-10 Скачать руководство пользователя страница 58](http://html1.mh-extra.com/html/sma/clcon-10/clcon-10_installation-manual_1294241058.webp)
6.12.5.2 Connecting a Remote Terminal for Feedback via Digital Signal
Using suitable remote terminals (e.g. optical or acoustic signal generators), the status of the system
can be fed back to you via the pin groups
Digital output 1
,
Digital output 2
, and
Digital
output 3
of the
X2
terminal. Which feedback options were set at the factory for terminal
X2
and
its pin groups, is described in a previous section (see Section 6.2, page 26). The feedback options
that you can choose from can be found in the menu
Settings
on the user interface of the
Cluster Controller.
Observe the maximum load capacity of the relay contacts
The relay contacts may be loaded with a maximum switching power of 30 W and a maximum
voltage of 48 V
DC
.
Requirements:
☐ The remote terminal must be technically suitable for connection to the digital output (see
☐ The connection cable must be prepared for connection to the multipole plug (see Section 6.5,
Figure 26: Pin assignment for the pin groups
Digital output 1
,
Digital output 2
, and
Digital output 3
Pin group
Relay
Pin
Signal
Explanation
Digital output 1
A
A1
NC
Back contact
A2
CO
Change-over con-
tact
A3
NO
Front contact
Digital output 2
B
A4
NC
Back contact
A5
CO
Change-over con-
tact
A6
NO
Front contact