![SMA CLCON-10 Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/sma/clcon-10/clcon-10_installation-manual_1294241080.webp)
Digital outputs
Quantity
3
Design
Potential-free relay contacts
Maximum switching power
30 W
Maximum voltage load
48 V
DC
Maximum cable length
30 m
Analog inputs
Number of analog inputs for current signals
3
Number of analog inputs for voltage signals
1
Internal resistance
450 Ω
Measurement range for current signals
0 mA to 20 mA
Measurement range for voltage signals
0 V to +10 V
Typical tolerance
± 0.3%
Maximum tolerance
± 2%
Maximum cable length
30 m
Analog outputs
Number of analog outputs for current signals
3
Measurement range for current signals
4 mA to 20 mA
Maximum tolerance
± 0.5%
Maximum cable length
3,000 m
Temperature Inputs
Quantity
2
Measuring shunt
Platinum sensor Pt100, platinum sensor Pt1000
Type of measurement
Two-conductor connection technology, four-
conductor connection technology
Measurement range
-40°C to +85°C
Maximum tolerance*
±0.5°C
Maximum cable length*
20 m
* when measured with four-conductor connection technology