6.5.8.3
Activating the Manual Resume Mode
If the inverter is switched off due to a grid limit infringement, you can prevent an automatic restart of the inverter. Only
once the error has been acknowledged will the inverter switch back on. You can activate the Manual Resume Mode
for individual errors of grid limit infringement. You can read off the reason for the current restart block in the
instantaneous value
ManResStt
.
Procedure:
1. Call up the parameter overview (see Section 12.8.3, page 178).
2. To activate the Manual Resume Mode for individual disturbances, set the desired parameters to
On
:
Manual Resume Mode after
Parameter
Disconnection due to overvoltage
ManResOvrVol
Disconnection due to undervoltage
ManResUndrVol
Disconnection due to overfrequency
ManResOvrFrq
Disconnection due to underfrequency
ManResUndrFrq
Disconnection due to passive islanding detection
ManResPID
Disconnection due to disturbance in a line conductor
ManResPLD
3. Save the parameter changes (see Section 12.8.4, page 178).
6.5.9
Setting the Grid Support
6.5.9.1
Setting Full and Limited Dynamic Grid Support (FRT)
1. Call up the parameter overview (see Section 12.8.3, page 178).
2. Set dynamic grid support with the parameter
FRTEna
.
3. Set operating mode for dynamic grid support with the parameter
FRTMod
.
4. Set deactivation delay for LVRT with the parameter
FRTSwOffTm
.
5. Set the scaling of the k factor for LVRT with the parameter
FRTArGraNom
.
6. Set the upper limit of the voltage deadband with the parameter
FRTDbVolNomMax
.
7. Set the lower limit of the voltage deadband with the parameter
FRTDbVolNomMin
.
8. In operating mode FRT_SDLWindV, set the gradient for the FRT characteristic curve in case of overvoltage with the
parameter
FRT2ArGraNomHi
.
9. For the operating mode FRT_SDLWindV, set the gradient for the FRT characteristic curve in case of undervoltage
with the parameter
FRT2ArGraNomLo
.
10. Save the parameter changes (see Section 12.8.4, page 178).
6.5.9.2
Setting Enable Islanding Detection
1. Call up the parameter overview (see Section 12.8.3, page 178).
2. Set the islanding detection with the parameter
EnaAid
.
3. Save the parameter changes (see Section 12.8.4, page 178).
6 Commissioning
SMA Solar Technology AG
System Manual
87
MVPS22JP-SH-en-11