Name
Description
Value/range
Explanation
Default
value
WGraEna**
Activation of the active
power change gradient
Off
Deactivated
On
On
Activated
WGraRe-
conEna**
Activation of the decou-
pling protection ramp for
reconnection
Off
Deactivated
Off
On
Activated
P-VtgGraNom
**
Active power gradient
for voltage-dependent
active power limitation
0.017%/s to
100.000%/s
‒
0.166%/s
P-VtgEna
Activation of voltage-de-
pendent active power
limitation
Off
Deactivated
Off
On
Activated
P-VtgNomP1
Voltage at point 1
100% to 120%
‒
111%
P-VtgNomP2
Voltage at point 2
90% to 120%
‒
110%
P-VtgAtMin
Minimum active power
with voltage-dependent
active power limitation
0% to 100%
‒
20%
PwrApLimitPrio
***
Prioritization of reactive
power or active power
PrioPwrRtPrioPwrRt
Prioritization of reactive power
PrioPwrRtPri-
oPwrRt
PrioPwrAt
Prioritization of active power
SDLimComSrc
***
Selection of the SDLimit
source
CAN
Interface of the communication
unit
UART
UART
Via SMA Net
P-WSubVal
Substitute value for ac-
tive power limitation out-
side of normal feed-in
operation during commu-
nication disturbance
0 kW to 1,000 kW
Sunny Central 500CP-JP
500 kW
Sunny Central 630CP-JP
700 kW
Sunny Central 800CP-JP
880 kW
Q-VArSubVal
Substitute value for reac-
tive power setpoint out-
side of normal feed-in
operation during commu-
nication disturbance
−220 kVAr to
+220 kVAr
Sunny Central 500CP-JP
0 kVAr
−310 kVAr to
+310 kVAr
Sunny Central 630CP-JP
−385 kVAr to
+385 kVAr
Sunny Central 800CP-JP
PF-PFSubVal
Substitute value for cos φ
outside of normal feed-in
operation during commu-
nication disturbance
0.5 to 1
The value 0.5 cannot be reached
in normal operation.
1
PF-PFExtSubVal Substitute value for exci-
tation type during com-
munication disturbance
OvExt
Overexcited
OvExt
UnExt
Underexcited
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
227
MVPS22JP-SH-en-11