Ref : 26702 30 07/01/15
Err8
Mains undervoltage fault (less than 155V)
Blocks the motor commands as long as the voltage is too low.
Check the mains.
Err9
Logic card and power card incompatible
Blocks the motor commands.
Power card version unsuitable for the command card version :
The command card version was upgraded without changing the power
card version. Reprogram the cards in the factory.
Err10
Hall effect sensor fault or bad motor choice
Operation goes into fail soft mode ; vibrations occur when the door
is at the end stop.
Encoder read fault : Hall effect sensors defective or disconnected.
Make sure that the parameters are not set for a Brushless motor
when an Asynchronous motor is in operation.
Check the wiring of the Hall effect sensors if a Brushless motor is
used.
ENCODER POSITION DISPLAY
To make sure that the counting operates correctly (particularly if an
Err6
fault present), the counting value may be viewed during the operation in
the
Position
display mode.
The repeatability of the value 0 in opening operations and that of the value
of the maximum travel value in closing operations may be checked.
To do this, simply select the
Position
display mode.
To go into the Position display mode :
Press
displays the encoder position "
0000
"
To set the display mode, press
Then you can execute the CMD commands to analyse the counting values
which are displayed.
NUMBER OF CYCLES DISPLAY
The card totalises the number of cycles (o closing) performed
since its commissioning displayed in thousands of cycles in the
CYCL
parameter
.
This value may not be reset to zero.
To access the cycle counter, proceed as follows :
Scroll the menus by successively pressing
Select
PARA
by pressing
.
Scroll the parameters with
to
CYCL
To display
CYCL
, press
.