SerVice anD inStallation Manual

2.3

2.3

anti-Two-Block Switch

anti-Two-Block Switch

Verify the anti-two-block switch is programmed in

the LMS display. Switches shipped with displays

are  pre-programmed  in  the  factory. 

Test:  if  the

switch has been programmed to the display then

the display will go into two-block alarm when the

switch is released

. Press 

Mute

to silence the alarm

until the next two-block event or simulation. If the

switch has not been programmed to the display,

this  should  be  done  before  proceeding  with

installation. See the section 

how to add a Sensor

to the lMS

.

2.3a Switch Bracket installation 

Install the LS051 on the pipelayer boom near the tip

with a threaded chain connector. Install a weight and

chain  assembly  to  the  bottom  eye  bolt.  The

maximum  total  weight  of  the  weight  and  chain

assembly supported by the LS051 anti-two-block

switch is 20 lb.

2.3b chain length adjustment

1. Chain length adjustment № 1 – minimum boom angle

a. At  minimum  boom  angle,  with  no

additional weight on the hook block and

one  part  of  line  only,  lift  the  boom  just

enough to have the hook block suspend

and clear the sensor chain and weight.

b. Hoist slowly until the buzzer sounds. Note

the  hoisting  distance  remaining;  this

distance must be great enough to allow

the operator and the lockout system, if

installed, to prevent a two-block event. If

necessary, add chain between the sensor

and weight to increase warning distance.

If  still  insufficient,  contact  your  service

representative.

2. Chain length adjustment № 2- maximum boom

angle

a. Raise the boom to the maximum angle.
b. Hoist  slowly  as  described  in 

Step  1.b

.

Verify that the warning distance is equal

to or greater than that determined at the

minimum boom angle.

3. Chain  length  adjustment  №  3  –  speed  test:

Lower the boom until the weight height becomes

visually clear to the operator. Repeatedly create

two-block,  progressively  hoisting  faster,  to

ensure that the warning and lockout work within

acceptable  amount  of  time  and  distance.

Increase the length of the chain if needed.

Figure: anti-two-block switch

B) Hook block stops
rising, two-block
prevented with
safety margin

Boom

base

A) Anti-two-block
switch triggers
two-block alarm

Boom

base

Figure: chain length test at minimum angle

Increase

GS050

weight

Figure: chain length adjustment

IMPORTANT!

To increase chain length, only use

lightweight chain.

!

!

SkyAzul, Equipment Solutions

www.skyazul.com

301-371-6126

Содержание Trimble/LSI GM820

Страница 1: ...Trimble LSI GM820 Volvo With GS820 Display and Wireless Sensors Installation and Service Manual...

Страница 2: ......

Страница 3: ...y information which is protected by copyright and all rights are reserved No part of this document may be photocopied reproduced or translated to another language without the prior written consent of...

Страница 4: ......

Страница 5: ...tion lockout at 110 C Slope indicator show the pipelayer level d Slew indicator the arrow points toward the uphill direction The quadrant refers to the pipelayer upper body position The left side of t...

Страница 6: ...using Back next up and Down as described in password settings section and press enter alarm red lamp level All programmed and rated capacity limits and two block will generate an audible alarm when t...

Страница 7: ...e is available B0211_V1012 Sxxx zip It contains all the language packs mentioned above example if a system with the default language pack must be switched to Chinese 1 Download the language packs if i...

Страница 8: ...t be in contact with any metal object d The transmitter antenna should point to the left of the boom when viewed from the cab it should not point directly to or away from the display 2 Weld the mounti...

Страница 9: ...and clear the sensor chain and weight b Hoist slowly until the buzzer sounds Note the hoisting distance remaining this distance must be great enough to allow the operator and the lockout system if in...

Страница 10: ...t angle indication accordingly 2 4a angle calibration procedure 1 Mechanical Set up 1 Level the boom such that it is perfectly horizontal use a high quality bubble or digital angle sensor If the LMS d...

Страница 11: ...araMeter aDjuStMent 5 Use up and Down to select the angle sensor to be calibrated and press enter 6 Select 2 triM and press enter to modify 7 Use up and Down to modify the trim value example If angle...

Страница 12: ...Determine the sensor to be removed If more than one sensor of the same type has been added to the sensor list then determine the radio identification number ID of the sensor to be removed before proce...

Страница 13: ...munication with the sensor is possible and to start the wizard 4 Use up and Down to adjust the actual parts of line on the load sensor and then press enter to confirm 5 Note the units that will be use...

Страница 14: ...ed 4 Verify list and trim angle indication in the operation display They should change as shown in the picture For calibration use one of the two procedures below Minimum and maximum limits for list a...

Страница 15: ...o to menu 4 inStallation and select 4B SenSor caliBration 3 Enter the user password aza and press enter 4 Select 4B1 autoMatic caliBration WizarD 5 Use up and Down to select the trim or list sensor 6...

Страница 16: ...de the data logger analyzes the measured weight and records the peak value only One threshold per load cell must be adjusted When the weight drops by more than the peak threshold the peak weight is re...

Страница 17: ...nd will then have teh same ID It is the case for the load and anti two block A2B and for the trim list angles how to restore default factory settings It is possible to return the display to its factor...

Страница 18: ...Alternatively to the above access menu 5e digital input to see the status of the two digital input signals No 1 Mute input Off On No 2 Rigging mode input Off On System Sensors Diagnostic 1 Go to menu...

Страница 19: ...dition Verifythewireconnection RefertothePowerSupply and Lockout Connection sub section of this manual alert VeriFy White Wire ShorteD to GrounD description Voltage is not detected on the lockout wire...

Страница 20: ...on the key but its size is 0 kB Solution Did the transfer complete successfully Try again Problem The following message appears on screen during the transfer unaBle to create File replace uSB Solutio...

Страница 21: ...b Only dtl files generated by the LMS data logger can be displayed 4 3c Full report To export the full report to Excel click on the Full Report button in the tool bar table Full report column headings...

Страница 22: ...do not overtighten 5 5 MainTenanCe MainTenanCe 1 4 in 1 2 Hex key 5 32 in Flat bladed screwdriver 5 New high quality D cell battery 3 6 V lithium or alkaline Figure remove the sensor box from the moun...

Страница 23: ...e the white nylon hex bolt to the middle of the length of the new antenna 8 Coat the exposed metal foot of the new antenna with an electrical insulating compound by carefully inserting it in the mouth...

Страница 24: ...o corrosion is visible on the battery holder inside the load cell transmitter If some trace of corrosion is visible rub it off gently and put a small amount of dielectric grease on each battery holder...

Страница 25: ...length of a length sensor 3 Verify radio communication see Radio communication troubleshooting section Battery diagnostic Go to menu 5a SySteM SenSorS DiaGnoStic Select a sensor and press enter to ver...

Страница 26: ...ad length parallel 16F Sheave radius 16G Deduct 4D chart SettinGS 1 Rated capacity indicator 2 Pipelayer capacity chart interpolation 3 Out of charts default working load limit 4 Enable start section...

Страница 27: ...noStic 5a SySteM SenSorS 5B raDio netWork 5B1 RADIO NETWORk 5B2 LAST SENSORS RECEIVED 5B3 SEARCh FOR SENSORS 5B4 BIT ERROR RATE TEST 5c lockout 1 A2B AND OVERLOAD 2 FREE SWING CUT 3 MUTE INPUT 4 RIGGI...

Страница 28: ......

Страница 29: ......

Страница 30: ...2 SkyAz l Equipment Solutions www skyazul com 301 371 6126 SkyAz l Inc 16 Walnut Street Middletown MD 21769 Phone 301 371 6126 Fax 301 371 0029 info skyazul com www skyazul com...

Отзывы: