DOL 834 CE
Technical User Guide
53
Cycle time
Relay heat. ON + OFF-time of the heating relay.
Minimum ON time
Relay heat. At heating requirement: The heating relay is ON for minimum this
time.
Minimum OFF time
Relay heat. When the heating relay is released, it is OFF for minimum this time.
P-band
0-10 V heating. Working range for 0-10 V heating.
Integration time
0-10 V heating. Reaction time for heating.
Longer time: slow reaction.
Shorter time: faster reaction.
Cooling
Cycle time
Relay cooling. ON + OFF time of the cooling relay.
Minimum ON time
Relay cooling. At cooling requirement: The cooling relay is ON for minimum this
time.
P-band
0-10 V cooling. Working range for 0-10 V cooling.
Integration time
0-10 V cooling. Reaction timer of the cooling.
Short time: Immediate reaction.
Long time: Slow reaction
Inlet
P band
With feedback. Working range of the ventilation
Accept band
Without feedback. Air intake is only regulated if the current position deviates
more than the tolerance band from the desired position.
Air inlet hysteresis
The position of the air intake changes when the current o hysteresis is
less/greater than the ventilation requirement needs.
Central exhaust
Select the menu
|
Technical | Service | Control parameters
Dynamic pres-
sure
Outside tempera-
ture
Pressure
When the outdoor temperature is low, the pressure in the ducting can be re-
duced. The required ventilation is achieved with the flaps fully open and a lower
fan output.
MultiStep correction
Min. switch point
When there is a requirement for 5% or more than the stepless unit can provide,
the system changes to the next MultiStep.
Stepless unit open
When switched, the stepless starts to open after this time
Stepless unit
closed
When switched, the stepless starts to close after this time.
Motor control open
When switched, a motor-controlled flap starts to open after this time.
Motor control
close
When switched, a motor-controlled flap starts to close after this time.
Air control open
When switched, an air-controlled flap starts to open after this time.
Air control close
When switched, an air-controlled flap starts to close after this time.
P band
Pressure control working range.
Integration time
Reaction time of the pressure control.