DOL 834 CE
28
Technical User Guide
With the function
Sensor alarm delay
, you can postpone the alarm signal so that
transient changes of the pressure level in the livestock house, e.g., when open-
ing a door, do not trigger the alarm.
The controller activates an alarm when the pressure in the livestock house
drops below or exceeds the settings of
Pressure low limit
/
Pressure high limit
.
You can connect and disconnect the alarms and set an alarm limit.
Dynamic Air
The Dynamic Air alarm is triggered in case of mechanical error. The house con-
troller triggers an alarm if the measurement of the ventilation output deviates
from the calculated ventilation requirement.
You can connect and disconnect the function.
The alarm may be due to a mechanical error in the fan, the pressure sensor or
the flap position.
Check the fan while it is running. Further troubleshooting must be carried out by
technically trained personnel.
Outlet alarms
Outlet alarms are technical alarms. The controller triggers an alarm if the flap
position of the air outlet deviates from the setting which the controller calculated
as correct.
You can connect and disconnect the alarm.
6.4.3 Alarms for auxiliary sensor
Alarm settings | Auxiliary sensors
Auxiliary sensor
The house controller triggers an alarm if the values for the sensor fall below or ex-
ceed the setpoints.
The sensors can be named in the menu
Technical | Manual installation | Man-
agement | Auxiliary sensors
.
6.5 Auxiliary alarms
It is possible to create a number of auxiliary alarms. For example, the controller may give an alarm from a con-
nected motor controller, a water pump or other equipment.
The alarms are set up in the menu
Alarm settings | Auxiliary | Auxiliary alarms | Auxiliary alarm settings
Press
Add
to add a new alarm.
Press the field
Name
to give the alarm a name.
Press
Category
to select the category the alarm belongs to.
Set the control mode
Hard
,
Soft
or
Disabled
.
Set a delay, if required.
Set the activation to take place in the event of high or low input.
Select if the alarm should be active always or from a specific
day number.
To delete an auxiliary alarm, press the icon .
After creating the alarm, see the menu
|
Installation
|
Show connection
for information about where to
connect the extra equipment.