DOL 834 CE
40
Technical User Guide
Runs before recalibration
Setting of the number of times the inlet flap has to run before it calibrates
automatically.
Minimum voltage
Maximum voltage
When the air outlets are 0-10 V controlled, the output voltage can be ad-
justed via the min. voltage as well as th max. voltage.
In the menu
Technical | Calibration | Central exhaust | Central exhaust air outlet flap
.
Select
ON
to start the calibration.
Check that the correct flap(s) open(s) and close(s) correctly.
Wait until the calibration is completed and the display shows
Ended
again.
Carry out the calibration in the same way for air outlet 2.
10.2 Calibration of current sensor
Set the calibration values to correspond to the used current sensor.
Value
Factory reset
Minimum voltage
0.0 V
Maximum voltage
10.0 V
Minimum value
0.0 A
Maximum value
10.0 A