Unit Configuration
Analogue Inputs
3 - 2
SKF Multilog On
-Line System IMx-S
User Manual
Figure 3 - 2.
IMx-S
I/O Board, Analogue I
nputs.
Table 3-2: Analogue terminal list.
The DIP switch settings for connected analogue sensors must be applied according to
the table below.
Table 3-3:
DIP switch settings for analogue sensors.
Signal
Terminal
DIP Settings
position: 123456
Standard
accelerometer (ICP)
N.C.
+ Signal/Pwr
Com.
Pwr
A
B
100110
Voltage source
N.C.
+ Signal
Com.
Pwr
A
B
000000
4–20 mA source
N.C.
+ Signal
– Signal
Pwr
A
B
000001
B
-sensor (4–20 mA
ouput)
+24 V
Signal
Com.
Pwr
A
B
100101
Eddy probe (–24 V)
–24 V
Signal
Com.
Pwr
A
B
011000
Voltage powered
sensor (max 35 mA)
+24 V
Signal
Com.
Pwr
A
B
100100
4–20 mA (IMx
powered)
+ Signal
– Signal
N.C.
Pwr
A
B
100101
N.C. = Not Connected
DIP switch setting 1 = ON, 0 = OFF