Introduction
IMx-S Unit
SKF Multilog On
-Line System IMx-S
1 - 3
User Manual
It is also possible to connect different types of on-line units in the same network, for
example, IMx-
S together with other IMx units and/or Mas
Con systems.
IMx-S Unit
Figure 1 - 2.
SKF Multilog On
-line System IMx-S 16 (left) and IMx-S 32 (right).
IMx-S 16
•
Up to 16 analogue channels
•
Up to 8 digital sensors, where 4 of the digital input channels are configurable for all
standard trigger sensors and 4 channels for square pulses with trigger level 12 to
24 V
•
Each IMx-
S 16 unit has 8 MB flash memory with the following storage capacity:
–
2 MB for firmware, configuration files, etc.
–
2 MB for trend value buffer
About 13 000 vibration trend values can be buffered.
Speed and process data use half the space of vibration.
–
4 MB for spectra and time signal buffer
About 250 spectra using 1 600 lines with phase and time signal can
be buffered.
If you use more lines, the number of spectrum is reduced.
If you use less lines, the number of spectrum is increased.
–
When the buffer gets full, the oldest data is thrown away.