![Sintrol Dumo Series Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/sintrol/dumo-series/dumo-series_user-manual_1283278070.webp)
©2021 Sintrol.
All rights reserved.
70 (104)
Revision 4
Figure 34: Display on the front panel of the device
See Table 14 for description of the front panel.
Table 14: Front panel of the device
①
7-segment display with four digits.*
•
In normal operation, indicates the measurement value.
•
In MAINTENANCE mode:
o
Position D0 indicates the active parameter number.
o
Positions D1 ... D3 indicate the parameter value.
②
Status LEDs.
* Display position labels D0 ... D3 are included in this manual for reference purposes only. They are not printed on the device.
9.2
Relay, LED and display functional logic
The device has various operation statuses that are indicated to the user with a combination of LEDs, two
relays and a 7-segment display with four digits.
9.2.1
Operation statuses
The operation statuses are described in Table 15:
Table 15: Operation statuses and their descriptions
Device status
Description
NORMAL OPERATION
•
The device operates normally according to the initial setup and
generates a valid output signal.
•
The output signal is below the configured thresholds for ALERT and
ALARM statuses.
ALERT
•
The device operates normally according to the initial setup and
generates a valid output signal.
•
The output signal is above the configured threshold for ALERT status.
•
The output signal is below the configured threshold for ALARM
status.