Click the SAVE button to store the new value in the device memory.
o
Select the option “SNT Slave”.
4.
Click the SAVE button to store the new settings in the device memory.
5.
Disconnect the device.
6.
Repeat steps 1 to 5 for each individual device in the network.
After you have adjusted the settings for each individual device according to the selected communication
protocol:
7.
Switch the terminator switch to ON position on the last device of the chain.
8.
Connect the first device of the chain to the communication base station.
•
If your device chain communicates through Modbus RTU protocol, the first device in the chain
must be connected to a Modbus master device.
•
If your device chain communicates through Sintrol Network protocol, the first device in the
chain must be connected to Sintrol Router or Network Router. The router device in turn must
be connected to a host computer.
The device network is now operational, and you can use the master device to control the devices.
8.3.3
Wireless device network
It is possible for multiple devices to communicate with each other using the optional radio frequency
(RF) communication protocol. The wireless connection operates on the Sintrol Network protocol, which
takes care of automatically forming the network. The measurement data is always transmitted using the
strongest available connection.
1
ON