6.2
Cable types
Make sure that the cables are suitable for the environment and industrial application
where the device is used. The cables must meet and be installed according to all
applicable local safety standards.
When choosing cables, consider the following:
•
Use a shielded cable if possible. Connect the cable shield to ground on one end only.
•
Minimum required conductor size is 0.3 mm
2
or 22 AWG.
•
The cables must withstand up to 75 °C (167 °F) continuous temperature.
The device uses screw-type wire-to-board terminal blocks for electrical connections. See Table 4 in
section