1.2.14 Adaptable Motor
t
The cooling fan and rotor shaft of general motor are coaxial, which results in
reduced cooling effect when the rotational speed declines. If variable speed is
required, add a more powerful fan or replace it with variable-frequency motor
in applications where the motor runs at low frequency for a long time.
t
The standard parameters of the adaptable motor have been configured
inside the AC drive. It is still necessary to perform motor auto-tuning or modify
the default values based on actual conditions. Otherwise, the running effect
and protection performance will be affected.
t
The standard adaptable motor is adaptable four-polo squirrel-cage AC
asynchronous induction motor or PMSM. For other types of motor, select a
proper AC drive according to the rated motor current.
t
The AC drive may alarm or even be damaged when short-circuit exists on
cables or inside the motor. Therefore, perform insulation short-circuit test
when the motor and cables are newly installed or during routine maintenance.
During the test, make sure that the AC drive is disconnected from the tested
parts.