●This setting will be memorized upon power failure.
●Either “
Other thermal
” or “
Optional E-Heater
” can be activated at the same time.
●There are two working logics for “
Optional E-heater”
.
Logic 1: either the heat pump or the optional electric heater can be started at the same time.
Logic 2: both the heat pump and the optional electric heater can be started at the same time after the
compressor has run for four minutes and T
Optional Water Temp
is equal to or lower than WOT-heat–Δt2.
2.4.8 Remote Sensor
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Remote sensor
”, the control panel will access to the
corresponding setting page, where it can be set to “
With
” or “
Without
”.
[Notes]
●This setting will be memorized upon power failure.
●Only when “
Remote sensor
” is set to “
With
”, the “
Ctrl. State
” can be set to “
T-room
”.
2.4.9 Air Removal
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Air removal
”, the control panel will access to the
corresponding setting page, where it can be set to “
On
” or “
Off
”.
[Notes]
● This setting will be memorized upon power failure.
● This setting can be done only when the unit is turned off. And when it is set to “
On
”, the unit is not allowed to
be turned on.
2.4.10 Floor Debug
[Operation Instructions]
1. At the commissioning parameter setting page, by touching “
Floor debug
”, the control panel will access to the
corresponding setting page.
2. At the setting page, “
Floor debug
”, “
Segments
”, “
Period 1 temp
”, “
Segment time
”, and “
ΔT of segment
”
can be set.