23
been put into operation, this function is unavailable, alerting “
Wrong operation
”.
● This function will not be memorized upon power failure.
2.4.17 Control Logic of the Water Tank Heater
[Operation Instructions]
At the commissioning parameter setting page, by touching “
Tank heater
”, it will access to the setting page of
control logic for the water tank heater.
[Notes]
● “Reserved” will be displayed when the water tank is unavailable.
● This setting can be done only when the unit is off.
● This function can be memorized upon power failure.
● Logic 1: NEVER allowed the Unit’s Compressor and the Water Tank Electric Heater or the Optional Electric
Heater to work at the same time.
● Logic 2: While Heating/ C Hot water mode (Hot Water priority) Tset ≥ ΔThot water +2, when
water tank temperature reach THPmax, the water tank EH will be ON and start to do hot water, at the same time,
the compressor wil turn to heating/cooling mode, water tank EH and Compressor will be ON together.
2.4.18 Parameter Setting
[Operation Instructions]
At the commissioning parameter setting page, by touching “
PARAM.
”, it will access to the pages as shown
below.
Page of Commissioning Parameters
At this page, select the desired option and then go to the corresponding page.
After that, by pressing “
OK
”, this setting will be saved and then the unit will run based on this setting; or by
pressing “
Cancel
”, this setting will not be saved and quit.
No
Full Name
Display
Name
Range
Default
Remark
1
T-HP max
T-HP max
40~55
℃
104~131°F
50
℃
/122°F
It is unavailable to mini chillers.
2
Cool run
time
Cool run
time
1~10min
3min
[2-way valve Off]
When “Cool run time” has expired
and temperature difference keeps
at the standby zone, the unit
will stop.It is unavailable to mini
chillers.
5min
[2-way valve On]
3
Heat run
time
Heat run
time
1~10min
3min
[2-way valve Off]
When “Heat run time” has expired
and temperature difference keeps
at the standby zone, the unit will
stop.
5min
[2-way valve On]
[Notes]
● For parameters with different defaults at different conditions, once the current condition changes, the
corresponding default also will change.