14
Parameter Setting Page
2. At the menu setting page, by touching the page turning keys, it is able to switch to the page where the desired
parameter is.
3. After that, this setting will be saved by touching “OK” and then the unit will run based on this setting. While
this setting will give up by touching “Cancel”.
[Notes]
For parameters with different defaults under different conditions, when conditions changes, the default value
also will change as the corresponding condition changes.
All parameters will be memorized upon power failure.
Parameter Setting
No
Full Name
Displayed
Name
Range
Range
Default
Remarks
(
℃
)
(°F)
1
Leaving water
temperature for
cooling(T1)
WOT-Cool
7~25
℃
45~77°F
18
℃
/64°F
Unavailable to heating
only units
2
Leaving water
temperature for
heating (T2)
WOT-Heat
20~60
℃
68~140°F
45
℃
/113°F
High-temp series units
20~55
℃
68~140°F
45
℃
/113°F
Normal-temp series
units
3
Room temperature
for cooling (T3)
RT-Cool
18~30
℃
64~86°F
24
℃
/75°F
Unavailable to heating
only units
4
Room temperature
for heating (T4)
RT-Heat
18~30
℃
64~86°F
20
℃
/68°F
/
5
Water tank
temperature(T5)
T-water tank
40~80
℃
104~176°F
50
℃
/122°F
Unavailable to mini
chillers
6
Leaving water
temperature
difference for cooling
(Δt1)
ΔT-Cool
2~10
℃
36~50°F
5
℃
/41°F
Unavailable to mini
chillers
7
Leaving water
temperature
difference for cooling
(Δt2)
ΔT-Heat
2~10
℃
36~50°F
10
℃
/50°F
/
8
Leaving water
temperature
difference for water
heating (Δt3)
ΔT-hot water
2~8
℃
36~46°F
5
℃
/41°F
Unavailable to mini
chillers
9
Room temperature
control difference
(Δt4)
ΔT-Room temp
1~5
℃
34~41°F
2
℃
/36°F
/