19
Logic 1
1. The set point of other thermal should be equal to that of “
WOT-Heat
” in “
Heat
” mode and “
Heat + hot
water
”mode; The set point should be the smaller one between “
T-Water tank
” +5°C and 60°C in “
Hot water
”
mode.
2. The water pump for other thermal must be always active under the “Heat” mode.
3. Under the “
Heat
” mode, the 2-way valve will be controlled based on the setting of the control panel. During
heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water
pump will start but the other thermal will stop.
Under the “
Hot water
” mode, the 3-way valve will switch to the water tank, the water pump of the heat pump will
always stop but the other thermal will start.
Under the “
Heat + Hot water”
mode, the other thermal only works for space heating, and the electric heater
of the water tank works for water heating. In this case, the 2-way valve is controlled base d on the setting of the
control panel, and the 3-way valve will always stop. During heating operation, the water pump of the heat pump
unit will be stopped; however, during standby status, the water pump will start.
Logic 2
1. The set point of other thermal should be equal to that of “
WOT-Heat”
and both are or lower than 60
℃
in “
Heat”
mode and “
Heat + hot water
”mode; The set point should be the smaller one between “
T-Water tank
” +5°C and
60°C in “
Hot water
” mode.
2. The water pump for other thermal must be always active under the “
Heat
” mode.
3. Under the “
Heat
” mode, the 2-way valve will be controlled based on the setting of the control panel. During
heating operation, the water pump of the heat pump unit will be stopped; however, during standby status, the water
pump will start but the other thermal will stop.
Under the “
Hot water
” mode, the 3-way valve will switch to the water tank, the water pump of the heat pump will
always stop but the other thermal will start.
Under the “
Heat + Hot water
” mode ("
Heat
" takes the priority), the other thermal only works for space heating,
and the electric heater of the water tank works for water heating. In this case, the 2-way valve is controlled base d
on the setting of the control panel, and the 3-way valve will always stop. During heating operation, the water pump
of the heat pump unit will be stopped; however, during standby status, the water pump will start.
Under the “
Heat + Hot water
” mode ("
Hot water
" takes the priority), the other thermal works for space heating
and water heating. The other thermal will work for water heating firstly, after reached “
T-water tank
”, other thermal
turns to space heagting.
Logic 3
The heat pump will only send a signal to other thermal, but all the logic of control must be “
stand alone
”.
2.4.7 Optional E-Heater
[Operation Instructions]
1. At the commissioning parameter setting page, by touching “
Optional E-Heater
”, the control panel will access
to the corresponding setting page.
2. At the “
Optional E-Heater
” setting page, it can be set to “
1
”, “
2
” or “
Off
”.