1) Label descriptions are given in Table 8-7
8.4 Outdoor unit PCBs
8.4.1 MAIN PCB
20
1
22
2
3
4
5
7
6
8
9
10
11
13
14
16
18
19
21
23
24
25
26
27
28
29
30
31
32
34
35
36
33
37
38
39
40
43
44
12
17
Fig. 8-7 Main PCB of
SCV-300EB
and
SCV-600EB
41
15
42
CN6:ST1,Four-way valve
CN86:SV2,Spray cooling valve
NO.
1
2
3
4
5
6
7
8
9
10
Detail information
CN30
:
Input of three-phase four-wire power supply (fault code E1) Input of transformer, 220-240V AC
current. (only valid for the main unit) Three phases A, B and C of power supply should exist 120° among
them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will
be displayed. When the power supply returns to normal condition, fault is removed. Attention: phase lace
and phase dislocation of power supply are detected only in the early period after the power supply is
connected, and they are not detected while the unit is in operation.
CN12:Quick return oil solenoid valve
CN5:EVA-HEAT,Water side heat exchanger heaters connection
CN13:EVA-HEAT,Electric of water side heat exchanger heaters connection
CN42:CCH,Crankcase heater
CN43:CCH,Crankcase heater
Table 8-4
CN4/CN11:W-HEAT,Electric heater of water flow switch
CN83:Pump
1
)
After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always
in the process of operation.
2
)
In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop
operating.
3
)
In case of shutdown under the pump mode, the pump can be directly shut down.
14
Содержание SCV EB Series
Страница 1: ...AIR COOLED CHILLER UNIT INSTALLATION AND USER MANUAL SCV XXX B AIR CONDITIONING...
Страница 2: ...Original instructions...
Страница 3: ......
Страница 49: ......
Страница 50: ...NOTE 44...
Страница 51: ......
Страница 52: ...0 1 234 56 0 7 8 234 0 9 1 7 1 0 6 16 3 5 9 4 260 88 4 260 88 08 88 688 0 4 08 4 6 4A8 60 B...