8.6.3 Design of the store tank in the system
Model
SCV-300EB
SCV-600EB
Pipe connection methods
Screwed connection
Hoop connection
Specifications of water pipe
DN40
DN50
Specifications of screw thread
Rc 1 1/4
/
8.6.2 Connection mode of pipe
The water inlet and outlet pipes are installed and connected as shown in the following figures.
SCV-300EB
model uses
screwed connection, while the
SCV-600EB
model uses hoop connection. For the specifications of the water pipes and
screw thread, see the Table 8-7 below.
Table 8-7
Fig.8-20 connection mode of
SCV-300EB
pipe
Fig.8-21 connection mode of
SCV-600EB
pipe
kW is the unit for cooling capacity and L is the unit for G, water flow in the formula counting the minimum water flow.
Comfortable air conditioner
G= cooling capacity×3.5L
Process cooling
G= cooling capacity×7.4L
In certain occasion (especially in manufacture cooling process), for conforming the system water content requirement,
it’s necessary to mount a tank equipping with a cut-off baffle at the system to avoid water short-circuit, Please see
the following schemes: