Control
Page 53 Total 145
[Notes]
●When “
Weekly timer
”, “
Preset mode
”,“
Clock timer
” “
Temp. timer
” have been set at the same time,
then the latter takes the priority.
●This setting is valid only when the unit is turned on.
●Under the “
Cool
” or “
Cool+Hot water
” mode, the setting targets at “
WT-Coo
l”; while under the “
Heat
”
or “
Heat+Hot water
” mode, the setting targets at “WT-Heat”.
●When start time of period 2 is the same as that of period 1, then the former takes prevalence.
●”Temp.timer” is judged based on timer.
●During this setting, when temperature is set manually, then this setting will take prevalence.
●Under the “Hot water” mode, this function will be reserved.
● This function will be memorized upon power failure.
3.2.2.12 Emergen. Mode
[Operation Instructions]
★
At the function setting page, set the mode to “
Heat
” or “
Hot water
”.
★
At the
function setting page, select “
Emergen.mode
” and set it to “
On
” or “
Off
”.
★
When “
Emergen.mode
” has activated, the corresponding icon will appear at the upper side of the
menu page.
★
When the mode is not set to “
Heat
” or “
Hot water
”, the display panel will tell “
Wrong running mode!
”
[Notes]
● The emergency mode is allowed on conditions that there is some error or protection and the
compressor has stopped at least for three minutes. If the error or protection has not been recovered,
the unit can access to the emergency mode through the wired controller (when the unit is off).
● Under the emergency mode, “
Hot water
” or “
Heat”
cannot be performed at the same time.
● When the running mode is set to “
Heat
”, if “
Other thermal”
or “
Optional E-Heater
” is set to
“
Without
”, the unit will fail to access to the “
Emergen. mode
”.
●When the unit performs “
Heat
” under “
Emergen. mode
” and the controller detects “
HP-Water
Switch
”, “
Auxi. heater 1
”, “
Auxi. heater 1
”, and “
Temp-AHLW
”, this mode will quit at once. In the
same way,
when errors mentioned above occur, “
Emergen. mode
” cannot be activated.
●When the unit performs “
Hot water
” under “
Emergen. mode
” and the controller detects “
Auxi.-WTH
”,
this mode will quit at once. In the same way, when errors mentioned above occur, “
Emergen. mode
”
cannot be activated.
●When this function has been activated, “
Weekly timer
”, “
Preset mode
”, “
Clock timer
”,and “
Temp
timer
” will be deactivated. Beside “
On/Off
”, “
Mode
”, “
Quiet mode
”, “
Weekly timer
”, “
Preset mode
”,
“
Clock timer
”,and “
Temp timer
” operation are unavailable.
●Under “
Emergen. mode
”, the thermostat does not work.
●This function can be activated only when the unit is turned off. If dosing so with the unit keeping “
On
”,
Содержание S-THERM GSH-100ERB
Страница 5: ...Engineering Data Page 1 Total 145 ENGINEERING DATA...
Страница 15: ...Engineering Data Page 12 Total 145 2 Outline Dimensions GSH 60IRB GSH 80IRB GSH 100IRB...
Страница 16: ...Engineering Data Page 13 Total 145 GSH 80ERB GSH 100ERB GSH 60ERB...
Страница 18: ...Engineering Data Page 15 Total 145 SMH 80ERB...
Страница 21: ...SMH 100ERB Engineering Data...
Страница 23: ...SMH 60IRB...
Страница 24: ...SMH 60ERB...
Страница 26: ...Design and Selection Page 19 Total 145 DESIGN SELECTION...
Страница 40: ...Control Page 33 Total 145 UNIT CONTROL...
Страница 41: ...Control Page 34 Total 145 1 Integral Control Concept 1 1 Control Principle Diagram Control Diagram...
Страница 83: ...Control Page 76 Total 145 2 Open Ewpe Smart APP and click Sign up for registration...
Страница 85: ...Control Page 78 Total 145 4 Click at the right upper corner of homepage to add device...
Страница 88: ...Control Page 81 Total 145 3 3 2 Setting of Main Functions 1 Set mode and temperature...
Страница 91: ...Control Page 84 Total 145...
Страница 92: ...Control Page 85 Total 145 3 3 3 2 Help Click Help and view the operation instructions of the APP...
Страница 93: ...Control Page 86 Total 145 3 3 3 3 Feedback Click Feedback to submit feedback...
Страница 94: ...Unit Installation Page 87 Total 145 UNIT INSTALLATION...
Страница 98: ...Unit Installation Page 91 Total 145 3 Service Tools Name Picture Spanner Screw Driver Pliers Tube Tongs...
Страница 103: ...Unit Installation Page 96 Total 145 4 4 Outline Dimension of Outdoor Unit GSH 80ERB GSH 100ERB GSH 60ERB...
Страница 104: ...Unit Installation Page 97 Total 145 GSH 60ERB GSH 80IRB GSH 100IRB...
Страница 112: ...Unit Installation Page 105 Total 145 4 6 4 Outline dimension of indoor unit...
Страница 118: ...Unit Installation Page 111 Total 145...
Страница 125: ...Unit Installation Page 118 Total 145 GSH 80ERB GSH 100ERB GSH 60ERB...
Страница 126: ...Unit Installation Page 119 Total 145 4 11 Wiring of the Terminal Board GSH 60IRB GSH 80IRB GSH 100IRB...
Страница 135: ...Test Operation Troubleshooting Maintenance Page 128 Total 145 TEST OPERATION TROUBLESHOOTING MAINTENANCE...