DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
2 OUTDOOR UNIT INSTALLATION
2.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or
internal damage, please immediately report to the transport company or equipment company in
writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the
specification and quantity of accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing
possible hazard. For the sake of protection and safety, it is suggested to move the unit with the
packaging box. Even though it is not permitted to do like this under special occasions, do not
remove the packaging box, thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of
the building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
2.2 Installation Site
To ensure the unit in proper function, selection of installation location must be in accordance with
following principles:
Outdoor unit shall be installed so that the air discharged by outdoor unit will not return and that
sufficient space for repair shall be provided around the machine.
The installation site must have good ventilation, so that the outdoor unit can take in and exhaust
enough air. Ensure that there is no obstacle for the return air inlet and exhaust of the outdoor unit. If
there is any obstacle blocking the return air inlet or exhaust, remove it.
Place of installation shall be strong enough to support the weight of outdoor unit, and it shall be able
to insulate noise and prevent vibration. Ensure that the wind and noise from the unit will not affect
your neighbors.
Avoid direct sunshine over the unit. It is better to set up a sun shield as the protection.
Place of installation must be able to drain the rainwater and defrosting water.
Place of installation must ensure the machine will not be buried under snow or subject to the
influence of rubbish or oil fog.
The installation site must be at a place where the air exhaust outlet does not face strong wind.
he outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect the
Содержание ASC-18A
Страница 2: ...last actualization 2011 ...
Страница 27: ...CONTROL ...
Страница 28: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation ...
Страница 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Страница 52: ...INSTALLATION ...
Страница 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Страница 94: ...DC INVERTER U MATCH AIR CONDITIONERS INSTALLATION ASGE 36AI ASD 36AI ASGE 36AI ASF 36AI ASGE 36AI ASC 36AI ...
Страница 102: ...96 MAINTENANCE ...
Страница 113: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 107 Malfunction display E3 Compressor Low Pressure Protection ...
Страница 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Страница 116: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 110 Malfunction display E6 Communications Failure ...
Страница 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Страница 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Страница 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Страница 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Страница 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Страница 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Страница 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Страница 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Страница 156: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 141 Model ASGE 36AI 3 ASGE 42AI 3 Model ASGE 36AI 3 S ...
Страница 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Страница 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Страница 219: ......
Страница 220: ...PARTS GUIDE CASSETTE FLOOR CEILING DUCT UNITS OUTDOOR UNITS OUTDOOR AND INDOOR UNITS DC INVERTER SERIES ...
Страница 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Страница 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Страница 228: ...Model ASGE 36AI ...
Страница 231: ...Model ASGE 36AI S ...
Страница 236: ...Model ASGE 36AI 3 S ...
Страница 238: ...Model ASGE 42AI 3 ...
Страница 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Страница 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Страница 246: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 24AI ASD 36AI ASD 36AI S ASD 42AI ASD 42AI ...
Страница 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Страница 251: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 24AI ASC 36AI ASC 36AI S ASC 42AI ASC 42AI S ...
Страница 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...