DC INVERTER U-MATCH AIR CONDITION MAINTENANCE
123
Tripping
◆
If the switching capacity can
meet the requirements?
Tripping
Tripped once energized
Tripped only after the
compressor is started?
Install the
electric switch
as required in
operating
instructions
1. Check if the cable connection L1, L2, L3
and N is correct.
2. Use multimeter to measure L1, L2, L3, N
and earthing wire for any short circuiting.
Procedures:
1) Check if the filter is burnt black
2) If the rectifier is damage.
3) If any other loads on complete unit are
short circuited or short circuited to ground.
3. Check if the AC contactor is stuck?
1. If the temperature of the environment
where the air switch is working is too high?
2. If the IMP module or compressor is short
circuited to ground?
3. If the IMP module or driver board is
damaged?
Record and feed
back
Yes
No
No
No
Yes
Yes
Содержание ASC-18A
Страница 2: ...last actualization 2011 ...
Страница 27: ...CONTROL ...
Страница 28: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation ...
Страница 47: ...DC INVERTER U MATCH AIR CONDITIONERS CONTROL 5 2 4 Dimensions ...
Страница 52: ...INSTALLATION ...
Страница 91: ...Wiring diagram ASGE 18AI main board WZD35B 30224042 ...
Страница 94: ...DC INVERTER U MATCH AIR CONDITIONERS INSTALLATION ASGE 36AI ASD 36AI ASGE 36AI ASF 36AI ASGE 36AI ASC 36AI ...
Страница 102: ...96 MAINTENANCE ...
Страница 113: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 107 Malfunction display E3 Compressor Low Pressure Protection ...
Страница 115: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 109 Malfunction display E5 Compressor Overheat ...
Страница 116: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 110 Malfunction display E6 Communications Failure ...
Страница 134: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 128 IPM module protection ...
Страница 135: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 129 DC busbar overvoltage protection ...
Страница 136: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 130 DC busbar undervoltage protection ...
Страница 137: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 131 Abnormal noise from PFC inductor ...
Страница 138: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 132 Radiator overheat protection ...
Страница 139: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 133 Tripping ...
Страница 143: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 137 Voltage protection of DC bus ...
Страница 155: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 36AI ...
Страница 156: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE 141 Model ASGE 36AI 3 ASGE 42AI 3 Model ASGE 36AI 3 S ...
Страница 157: ...DC INVERTER U MATCH AIR CONDITION MAINTENANCE Model ASGE 42AI 3 S Model ASGE 36AI S ...
Страница 158: ...Wiring diagram ASD 18AI old units BATCH CODE 18267 and 18756 main board 30228204 ...
Страница 219: ......
Страница 220: ...PARTS GUIDE CASSETTE FLOOR CEILING DUCT UNITS OUTDOOR UNITS OUTDOOR AND INDOOR UNITS DC INVERTER SERIES ...
Страница 221: ...4 Maintenance Exploded View and Spare Parts List Outdoor Unit ASGE 18AI ...
Страница 223: ...Model ASGE 24AI old model ASGE 24AI S ...
Страница 228: ...Model ASGE 36AI ...
Страница 231: ...Model ASGE 36AI S ...
Страница 236: ...Model ASGE 36AI 3 S ...
Страница 238: ...Model ASGE 42AI 3 ...
Страница 241: ...Model ASGE 42AI 3 S 1 PHASE ...
Страница 244: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 18AI ...
Страница 246: ...Exploded View and Spare Parts List DUCT UNITS Indoor Unit ASD 24AI ASD 36AI ASD 36AI S ASD 42AI ASD 42AI ...
Страница 249: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 18AI ...
Страница 251: ...Exploded View and Spare Parts List CASSETTE UNITS Indoor Unit ASC 24AI ASC 36AI ASC 36AI S ASC 42AI ASC 42AI S ...
Страница 255: ...Exploded View and Spare Parts List FLOOR CEILING UNITS Indoor Unit ASF 18AI ...