background image

 

 

 4 

S4100-0035-2 

 

5/02

Transponder Type 

Model  

Description 

Supv. 

Alarm 

4100-9600 

Basic Transponder, includes bay equipment with power distribution interface, and Basic 
Transponder Interface Module mounted in Block A 

87 mA 

87 mA 

normal  87 mA 

87 mA 

4100-9601 

Local Mode Transponder, includes bay equipment with power distribution 
interface, and Local Mode Transponder Interface Module mounted in Block A 

in local mode  112 mA  112 mA

Local Mode Controller Selection 

Model  

Description 

Supv. 

Alarm 

4601-9108 Flush 

mount 

4601-9109 Surface 

mount 

Red with white 
lettering 

normal  10 mA 

10 mA 

4601-9110 Flush 

mount 

4601-9111 Surface 

mount 

Beige with 
black lettering 

Local Mode Controller, 3-gang plate mounted; 
flush mount requires a 1-1/2” deep 3-gang 
box; surface mount controllers include a 
matching mounting box; refer to page 7 for 
details 

in local mode  20 mA 

60 mA 

Communication Modules 

Model  

Description 

Size 

Supv. 

Alarm 

4100-6031

 

City Circuit, with disconnect switches

 

20 mA 

36 mA 

4100-6032

 

City Circuit, without disconnect 
switches

 

For use with SPS 
only, not RPS 

20 mA 

36 mA 

4100-6033

 

Select one per SPS

 

Alarm Relay, 3 Form C relays, 2 A @ 32 VDC; for SPS or RPS

 

Mounts 

on SPS 

or RPS 

15 mA 

37 mA 

4100-6038

 

Dual RS-232 Interface

 

  1 Slot

 

132 mA 132 mA

4100-6045

 

Decoder Module

 

  3 Slots

 

85 mA  163 mA

4100-6048

 

VESDA

®

 Aspiration System Interface

 

  1 Slot

 

132 mA 132 mA

4100-9816  Master Clock Interface Module with one standard RS-232 port (see S4100-0033) 

  1 Slot

 

132 mA 132 mA

Expansion, System, Remote, and TrueAlert Power Supplies and Accessories* 

Model  

Voltage/Listing 

Description 

Size 

Supv. 

Alarm 

4100-5101

 

120 VAC 

UL 

4100-5103

 

120 VAC, Canadian 

ULC 

4100-5102 220-240 

VAC 

UL 

Expansion Power Supply (XPS);

 9 A output, 3 built-

in Class A/B NACs; Canadian models have low battery 
cutout

 

2 Blocks

 

50 mA 

50 mA 

4100-5115

 

NAC Expansion Module, 3 NACs, Class A/B, 

mounts on XPS only

 

N.A. 

25 mA 

25 mA 

4100-5111

 

120 VAC 

UL 

4100-5112

 

120 VAC, Canadian 

ULC 

4100-5113 220-240 

VAC 

UL 

System Power Supply (SPS);

 9 A power 

supply/charger with 250 point IDNet channel, 3 Class 
A/B NACs, and expansion slot for City Circuit or Alarm 
Relay option; Canadian model has low battery cutout

 

4 Blocks

 

175 mA 225 mA

4100-5125

 

120 VAC 

UL 

4100-5126

 

120 VAC, Canadian 

ULC 

4100-5127 220-240 

VAC 

UL 

Remote Power Supply (RPS);

 9 A power 

supply/charger similar to SPS except no IDNet channel 
or City Circuits, will accept one 4100-6033; Canadian 
model has low battery cutout

 

4 Blocks

 

150 mA 185 mA

4100-5120 120 

VAC 

UL 

4100-5121  120 VAC, Canadian 

ULC 

4100-5122 220-240 

VAC 

UL 

TrueAlert Power Supply (TPS);

 3 built-in Class B 

addressable Signaling Line Circuits (SLCs) rated 3 A 
each, built-in battery charger, with 2 A auxiliary power 
output tap; Canadian model has low battery cutout 

4 Blocks

 

88 mA  100 mA

4100-5124  TrueAlert SLC Class A Adapter for all 3 SLCs, 

mounts on TPS only

 

N.A. 

7 mA 

7 mA 

4100-5152  12 VDC Power Option, 2 A maximum 

1 Block 

1.5 A maximum 

4100-0636  Box Interconnection Harness Kit (non-audio); 

order one for each close-nippled cabinet

 

Miscellaneous Options and Accessories 

Model  

 Description

 

4100-1290 

24 Point I/O Module for external connections, select each point as either a switch input (momentary or maintained) or 
an output (for lamp/LED/relay); requires 1 Slot (refer to data sheet S4100-0032 for additional information) 

4100-0632  Terminal Block Utility Module; provides 2, 16 position terminal blocks mounted on 4” x 5” single block size, capable of 

up to 12 AWG wire (3.31 mm

2

4100-0633  Door Tamper Switch, connects into Transponder Interface Module, one per cabinet assembly if required 
4100-0634 120 

VAC 

4100-0635 220/230/240 

VAC 

Power Distribution Module (PDM) select per system voltage; 

one required per box

 

4100-9837 

Green LED Power-on Indicator Kit,

 required for 

ULC listing of MINIPLEX transponder

 

Mounts using knockout provided in solid door 

2081-9031 

Series resistor for type WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before 
tamper) 470 

, 1 W, encapsulated, two 18 AWG leads, 2 1/2” L x 1 3/8” W x 1” H (64 mm x 35 mm x 25 mm) 

* Power supply NACs can provide synchronized strobe or SmartSync™, two-wire operation.

 

Continued on next page 

 MINIPLEX Transponder Product Selection

 

Содержание SafeLINC 4100U

Страница 1: ...hingindicator Repeatoperationuntilallev ent s areacknow ledged Local tonewills ilenc e A B C A C Po wer D E F G H I J K L MN O P Q R S P 0 S T U V WX Y Z A LARMS Fi reAlarm P rio rity2Alarm S YST EM...

Страница 2: ...ode operation TrueAlarm device alarm LEDs will not operate Local Mode Control Operation Continued Notification Operation Fire alarm conditions reported against a fire alarm point type within a transpo...

Страница 3: ...ignals Syste m indicato r fla sh in g To ne On PressAlarmSile nce How to Reset System PressSys temRese t PressAcktosilen ceton e device ZONE 1 SIG 2 A UX 3 F B 4 IO 5 ID Net 6 P 7 A 8 L 9 N E T ADD R...

Страница 4: ...r supply charger with 250 point IDNet channel 3 Class A B NACs and expansion slot for City Circuit or Alarm Relay option Canadian model has low battery cutout 4 Blocks 175 mA 225 mA 4100 5125 120 VAC...

Страница 5: ...4100 1226 Flex 50 50 W Amplifier 25 VRMS output 4100 1227 Flex 50 50 W Amplifier 70 7 VRMS output Includes three on board Class B audio NACs power is supplied from an XPS RPS or SPS 100 W Digital Amp...

Страница 6: ...AC VDC 1 Slot 15 mA 75 mA 4100 3202 Four DPDT relays 10 A 250 VAC 2 Slots 15 mA 175 mA 4100 3203 Eight SPDT relays 3 A 30 VAC VDC These modules are nonpower limited and wiring must be routed away from...

Страница 7: ...5 4 mm into box For semi flush mounting use a 1 1 2 deep 38 mm 3 gang box Expansion Bay Module Loading Reference Description Mounting Transponder Interface Modules Block A Audio Riser Modules Block B...

Страница 8: ...6 stud Knockout screw nail holes for semi flush mounting Stud alignment markers each side Wall board reference for semi flush mounting 6 stud Optional semi flush trim kit reference Front view box outl...

Отзывы: