Module Bay Description 

 

Transponder model 4100-9600 

includes

 

a bay 

assembly, a power distribution interface module (PDI), a 
Basic Transponder Interface Module, and an interconnect 
harness. Communications with the host fire alarm control 
panel are via a Remote Unit Interface (RUI) connection 
that allows for up to 2500 ft (762 m) distance. RUI can 
communicate with up to a total of 31 remote devices and 
can be either Style 4 or Style 7 communications. 

Transponder model 4100-9601 

substitutes a Local 

Mode Transponder Module for the Basic Transponder 
Module. 

Optional Expansion Bays

 each include a PDI and 

accept a variety of optional modules for specific 
annunciator functions. 

The Battery Compartment

 (bottom) accepts two 

batteries, up to 50 Ah, that can be mounted within the 
cabinet. Battery mounting does not interfere with 
available module space. A power supply with battery 
charger is required for each battery set. 

Packaging Availability 

 

• 

Modules are power-limited (except as noted, such as 
relay modules) 

• 

Enclosure are available for either two or three bay 
sizes or for cabinet rack mounting 

• 

Boxes and solid doors are available in beige or red 
(ordered separately) 

• 

Up to eight close-nippled cabinets can be connected at 
one transponder location (close-nippled is mounted 
within 20 ft (6 m) and with interconnecting wiring 
enclosed in conduit) 

• 

Refer to document S4100-0037 for enclosure details 

Local Mode Control Operation 

 

Default Stand-Alone Operation.

 

In the event of a 

communications loss with the host fire alarm control 
panel, model 4100-9601 MINIPLEX Local Mode 
Transponders provide fire alarm response default 
operation for its connected devices and appliances per the 
following. 

Input Operation.

 During local mode operation, 

TrueAlarm initiating devices connected to the transponder 
will cause an alarm at their least sensitive alarm threshold.  

• 

Photoelectric sensors will alarm at 3.7%/ft smoke 
obscuration 

• 

Ionization sensors will alarm at 1.3%/ft obscuration 

• 

Heat sensors will alarm at a fixed temperature of 135° F 
(57° C).  

• 

NOTE:

 During local mode operation, TrueAlarm 

device alarm LEDs will not operate. 

 

Local Mode Control Operation 

(Continued)

 

 

Notification Operation.

 Fire alarm conditions reported 

against a fire alarm point type within a transponder in 
local mode will cause all notification appliance circuits in 
that transponder to: 

• 

Sound a general alarm temporal pattern horn tone 

• 

Activate visible notification appliance circuits 

Local Mode Module Support.

 Local mode operation 

provides support for the following 4100U modules:  

• 

System Power Supplies (SPS), Expansion Power 
Supplies (XPS), and Remote Power Supplies (RPS), 
including on-board notification appliance circuits 
(NACs) operated at a temporal pattern 

• 

TrueAlert Power Supplies (TPS) including the on-board  
signaling line circuits (SLCs) 

• 

IDNet addressable device circuits, including those 
on-board the SPS and IDNet expansion modules 

• 

4100U amplifiers will provide their on-board horn tones 
(500 Hz) at a temporal pattern through their on-board 
amplifier NACs 

Local Mode Operation Module Exclusion.

 Modules 

not listed above but that are listed as compatible with 
MINIPLEX transponders per this document, do not 
interfere with local mode operation but 

are

 

not supported

 

during local mode operation. 

Local Mode Controller 

 

Operation.

 During local mode operation, an optional 

Local Mode Controller will indicate status (see illustration 
below) and can be enabled using a keyswitch to perform 
local alarm silence or reset. If alarms occurring during local 
mode are reset using a Local Mode Controller, upon 
restoration of communications, 

those alarms will not be 

sent to the master controller

. If alarms are still present 

upon restoration of communications, then the alarm 
condition will be reported and host fire alarm control panel 
programmed alarm functions will occur. When 
communications are re-established, the local mode 
transponder restores automatically. 

Mounting.

 Local Mode Controllers are mounted on 

three-gang plates, are available in beige or red, and for 
either flush or semi-flush mounting. (See page 7 for 
details). 

Fire Alarm Local Mode Controller

ENABLE

CONTROL

Alarm

Alarm

Silenced

Local
Mode

Active

Power

On

Alarm

Silence

Reset

Local
Mode

Control

See Operating Instruction 579-343

 

Local Mode Controller Module 

 2 

S4100-0035-2 

 

5/02

Содержание SafeLINC 4100U

Страница 1: ...hingindicator Repeatoperationuntilallev ent s areacknow ledged Local tonewills ilenc e A B C A C Po wer D E F G H I J K L MN O P Q R S P 0 S T U V WX Y Z A LARMS Fi reAlarm P rio rity2Alarm S YST EM...

Страница 2: ...ode operation TrueAlarm device alarm LEDs will not operate Local Mode Control Operation Continued Notification Operation Fire alarm conditions reported against a fire alarm point type within a transpo...

Страница 3: ...ignals Syste m indicato r fla sh in g To ne On PressAlarmSile nce How to Reset System PressSys temRese t PressAcktosilen ceton e device ZONE 1 SIG 2 A UX 3 F B 4 IO 5 ID Net 6 P 7 A 8 L 9 N E T ADD R...

Страница 4: ...r supply charger with 250 point IDNet channel 3 Class A B NACs and expansion slot for City Circuit or Alarm Relay option Canadian model has low battery cutout 4 Blocks 175 mA 225 mA 4100 5125 120 VAC...

Страница 5: ...4100 1226 Flex 50 50 W Amplifier 25 VRMS output 4100 1227 Flex 50 50 W Amplifier 70 7 VRMS output Includes three on board Class B audio NACs power is supplied from an XPS RPS or SPS 100 W Digital Amp...

Страница 6: ...AC VDC 1 Slot 15 mA 75 mA 4100 3202 Four DPDT relays 10 A 250 VAC 2 Slots 15 mA 175 mA 4100 3203 Eight SPDT relays 3 A 30 VAC VDC These modules are nonpower limited and wiring must be routed away from...

Страница 7: ...5 4 mm into box For semi flush mounting use a 1 1 2 deep 38 mm 3 gang box Expansion Bay Module Loading Reference Description Mounting Transponder Interface Modules Block A Audio Riser Modules Block B...

Страница 8: ...6 stud Knockout screw nail holes for semi flush mounting Stud alignment markers each side Wall board reference for semi flush mounting 6 stud Optional semi flush trim kit reference Front view box outl...

Отзывы: