6
S4100-0035-2
5/02
Firefighters Telephone and General Audio Options
Model
Description
Size
Supv.
In Use
4100-1272
Expansion Telephone Control Module with three Class B telephone NACS;
required when telephone circuits are mounted in transponder;
1 Block
75 mA
329 mA
max.
4100-1273
Telephone Class A Adapter Module; mounts on 4100-1272; no additional current required
4100-2320
Audio Bay-to-Bay Interconnection Harness Kit;
order one for each audio bay addition
4100-0637
Audio Box Interconnection Harness Kit;
order one for each close-nippled audio cabinet
Initiating Device Circuits (IDCs)
Model
Description
Size
Supv.
Alarm
4100-5005
Eight zones, Class B
1 Slot
75 mA
195 mA
4100-5015
Eight zones, Class A
1 Slot
75 mA
195 mA
Addressable Interface Modules
Model
Description
Size
Supv.
Alarm
4100-3101
IDNet Module, 250 point capacity
With 250 IDNet devices, add
–
200 mA
250 mA
4100-3104 IDNet Module, 127 point capacity
With 127 IDNet devices, add
–
102 mA
127 mA
4100-3105 IDNet Module, 64 point capacity
With 64 IDNet devices, add
–
51 mA
64 mA
Module size 1 Block
Module without devices
–
75 mA
115 mA
IDNet Modules, Specifications for each capacity
Loading per IDNet device
–
0.8 mA
1 mA
Model
Description
Size
Supv.
Alarm
Module size 2 Slots
– –
Module without devices
–
270 mA
290 mA
Loading per MAPNET II device
–
1.7 mA
1.7 mA
4100-3102
MAPNET II Module, 127 point
capacity, add devices separately
Fully loaded module, total
–
470 mA
490 mA
4100-3103
MAPNET II Isolator Module, separates 127 input points into four isolated outputs,
mounts next to 4100-3102 only
1 Slot
50 mA
50 mA
Relay Modules
Model
Description
Size
Supv.
Alarm
4100-3201
Four DPDT relays, 2 A @ 30 VAC/VDC
1 Slot
15 mA
75 mA
4100-3202
Four DPDT relays, 10 A @ 250 VAC
2 Slots
15 mA
175 mA
4100-3203
Eight SPDT relays, 3 A @ 30 VAC/VDC
These modules are nonpower-limited
and wiring must be routed away from
power-limited wiring.
1 Slot
25 mA
280 mA
Current Calculation Notes:
1. To determine total supervisory current, add currents of modules in panel to base system value
and
all external loads powered
by panel power supplies.
2. To determine total alarm current, add currents of modules in panel to base system alarm current
and
add all panel NAC loads
and
all external loads powered from panel power supplies.
120 VAC Models
4 A maximum @ 102 to 132 VAC, 60 Hz
Input Power
[System (SPS); Expansion
(XPS); Remote (RPS); TrueAlert Power
Supplies (TPS); and 100 W amplifiers]
220-240 VAC Models 2 A maximum @ 204 to 264 VAC, 50/60 Hz;
separate taps for 220/230/240 VAC
Total Power Supply
Output Rating
9 A total @ nominal 28 VDC,
including module currents
and auxiliary power outputs
Auxiliary Power Tap 2 A maximum @ nominal 28 VDC
Power Supply
Output Ratings
(System, Expansion,
and Remote Power
Supplies)
NACs Programmed
for Auxiliary Power
2 A maximum per NAC, 5 A maximum @ nominal 28 VDC
Output switches to
battery backup
during mains AC
failure or brownout
conditions
Battery capacity range
6.2 Ah to 50 Ah; selectable via programming for batteries below 18 Ah; the SPS is
UL listed for up to 110 Ah battery charging for remotely located batteries
Battery Charger
(System and Remote
Power Supply)
Charger characteristics
and performance
Temperature compensated, dual rate, recharges depleted batteries within 48
hours per UL Standard 864, to 70% capacity in 12 hours per ULC Standard S527
Operating Temp. Range 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Range Up to 93% RH, non-condensing @ 90° F (32° C) maximum
MINIPLEX Transponder Product Selection
General Specifications