background image

 

S4100-0035-6  4/2005

Transponder Type 

Model

Description 

Supv. 

Alarm 

4100-9600 

Basic Transponder, includes bay equipment with power distribution interface, and 4100-0620 
Basic Transponder Interface Module mounted in Block A 

87 mA 

87 mA 

normal 

87 mA 

87 mA 

4100-9601 

Local Mode Transponder, includes bay equipment with power distribution 
interface, and 4100-0625 Local Mode Transponder Interface Module mounted in 
Block A 

in local mode  112 mA  112 mA

Local Mode Controller Selection 

(order as District P.O. from Space Age Electronics)

Model

Description 

Supv. 

Alarm 

4601-9108 Flush 

mount 

4601-9109 Surface 

mount 

Red with white 
lettering 

normal 

10 mA 

10 mA 

4601-9110 Flush 

mount 

4601-9111 Surface 

mount 

Beige with 
black lettering 

Local Mode Controller, 3-gang plate mounted; 
flush mount requires a 1-1/2” (38 mm) deep 
3-gang box; surface mount controllers include 
a matching mounting box; refer to page 7 for 
details

in local mode 

20 mA 

60 mA 

Communication Modules 

Model

Description 

Size

Supv. 

Alarm 

4100-6031

City Circuit, with disconnect switches

20 mA 

36 mA 

4100-6032

City Circuit, without disconnect switches

For use with SPS 
only, not RPS 

20 mA 

36 mA 

4100-6033

Select one per SPS

Alarm Relay, 3 Form C relays, 2 A @ 32 VDC; for SPS or RPS

Mounts

on SPS 

or RPS 

15 mA 

37 mA 

4100-6038

Dual RS-232 Interface

  1 Slot

132 mA

132 mA

4100-6045

Decoder Module

  3 Slots

85 mA 

163 mA

4100-6048

VESDA

®

 Aspiration System Interface

  1 Slot

132 mA

132 mA

4100-9816  Master Clock Interface Module with one standard RS-232 port (see S4100-0033) 

  1 Slot

132 mA

132 mA

Expansion, System, Remote, and TrueAlert Power Supplies and Accessories 

Model

Voltage/Listing 

Description 

Size

Supv. 

Alarm 

4100-5101

120 VAC 

UL 

4100-5103

120 VAC, Canadian 

ULC 

4100-5102 220-240 

VAC 

UL 

Expansion Power Supply (XPS);

 9 A output, 3 

built-in Class A/B NACs; Canadian models have low 
battery cutout*

2 Blocks

50 mA 

50 mA 

4100-5115

NAC Expansion Module, 3 NACs, Class A/B, 

mounts on XPS only

N.A. 

25 mA 

25 mA 

4100-5111

120 VAC 

UL 

4100-5112

120 VAC, Canadian 

ULC 

4100-5113 220-240 

VAC 

UL 

System Power Supply (SPS);

 9 A power 

supply/charger with 250 point IDNet channel, 3 Class 
A/B NACs, and expansion slot for City Circuit or Alarm 
Relay option; Canadian model has low battery cutout*

4 Blocks

175 mA

225 mA

4100-5125

120 VAC 

UL 

4100-5126

120 VAC, Canadian 

ULC 

4100-5127 220-240 

VAC 

UL 

Remote Power Supply (RPS);

 9 A power 

supply/charger similar to SPS except no IDNet 
channel or City Circuits, will accept one 4100-6033; 
Canadian model has low battery cutout*

4 Blocks

150 mA

185 mA

4100-5120 120 

VAC 

UL 

4100-5121  120 VAC, Canadian 

ULC 

4100-5122 220-240 

VAC 

UL 

TrueAlert Power Supply (TPS);

 3 built-in Class B 

addressable Signaling Line Circuits (SLCs) rated 3 A 
each, built-in battery charger, with 2 A auxiliary power 
output tap; Canadian model has low battery cutout 

4 Blocks

88 mA 

100 mA

4100-5124  TrueAlert SLC Class A Adapter for all 3 SLCs, 

mounts on TPS only

N.A. 

7 mA 

7 mA 

4100-5152  12 VDC Power Option, 2 A maximum 

1 Block 

1.5 A maximum 

4100-0636  Box Interconnection Harness Kit (non-audio); 

order one for each close-nippled cabinet

Miscellaneous Options and Accessories 

Model

Description

4100-1290 

24 Point I/O Module for external connections, select each point as either a switch input (momentary or maintained) or 
an output (for lamp/LED/relay); requires 1 Slot (refer to data sheet S4100-0032 for additional information) 

4100-0632 

Terminal Block Utility Module; provides 2, 16 position terminal blocks mounted on 4” x 5” single block size, capable of 
up to 12 AWG wire (3.31 mm

2

)

4100-0633  Door Tamper Switch, connects into Transponder Interface Module, one per cabinet assembly if required 

4100-0634 120 

VAC 

4100-0635 220/230/240 

VAC 

Power Distribution Module (PDM) select per system voltage; 

one required per box

4100-9837 

Green LED Power-on Indicator Kit,

 required for 

ULC listing of MINIPLEX transponder

Mounts using knockout provided in solid door 

2081-9031 

Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 
470

Ÿ

, 1 W, encapsulated, two 18 AWG leads (0.82 mm

2

), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm) 

* Power supply NACs can provide synchronized strobe or SmartSync, two-wire operation.

 

Continued on next page 

 MINIPLEX Transponder Product Selection

Содержание MINIPLEX 4100-9600

Страница 1: ...n Off Auto PressACKlocatedunderflashingindicator Repeat operationuntil allevents areacknowledged Localtonew ill silence AB C AC Pow er D E F G H I J K L M N O P Q R SP 0 S T U VW X Y Z ALARMS F ire Al...

Страница 2: ...sensors will alarm at a fixed temperature of 135 F 57 C x TrueAlarm device LEDs will be activated to indicate a device in alarm Local Mode Control Operation Continued Notification Operation Fire alar...

Страница 3: ...ashing Tone On Press Ala rmSilence How to Reset System Press Sy stemReset Press Ack tosilence tone device ZONE 1 SIG 2 AUX 3 FB 4 IO 5 IDNet 6 P 7 A 8 L 9 NET ADDR 0 DEL Enter C Exit Fire Alarm Ack Pr...

Страница 4: ...UL System Power Supply SPS 9 A power supply charger with 250 point IDNet channel 3 Class A B NACs and expansion slot for City Circuit or Alarm Relay option Canadian model has low battery cutout 4 Blo...

Страница 5: ...Model Output Voltage 25 VRMS 70 7 VRMS Power Supply Input Listing Description Details 4100 1328 4100 1329 120 VAC 60 Hz UL 4100 1330 4100 1331 120 VAC 60 Hz ULC 4100 1332 4100 1333 220 230 240 VAC 50...

Страница 6: ...102 MAPNET II Module 127 point capacity add devices separately Module size 2 Slots Loading per MAPNET II device 1 7 mA Fully loaded module total 470 mA 490 mA 4100 3103 Isolator Module for MAPNET II o...

Страница 7: ...20 ft 6 1 m 2 Nine wires required 24 VDC 2 one per LED indicator 4 and one per switch 3 3 Wire size 18 AWG 0 82 mm Expansion Bay Module Loading Reference Description Mounting Transponder Interface Mo...

Страница 8: ...r semi flush mounting 6 stud Optional semi flush trim kit reference Front view box outline without door Side view with door attached 2 Bay height 40 1016 mm Doors can be hinged left or right 3 Bay hei...

Отзывы: