10-8
Once the passcode has been entered, you may enter the Walk Test™ mode by performing the
following procedures.
1. Press the <MENU> key. The LCD shows the following message.
Press <NEXT> or <PREVIOUS> to Scroll
Change Access Level?
2. Press the <NEXT> key until the LCD displays the following message.
Press <NEXT> or <PREVIOUS> to Scroll
Enable Walk Test?
3. Press the <ENTER> key. The following message is displayed.
1 = on>OFF 2 = no>LOG 3 = ?>ZONE 4 = NO<sig
WALK TEST GROUP 0
4. Select the desired Walk Test™ data using keys <1> through <4>.
•
<1> Key -
Key <1> is used to toggle the Walk Test™ mode.
Turn Walk Test™ ON and OFF by pressing the <1> key. Pressing
this key causes an arrow to point to the active state (which is
displayed in capital letters).
•
<2> Key -
Key <2> is used to enable/disable logging of Walk
Test™ events. Walk Test™ events are logged into the Historical
Fault log if selected. Pressing this key causes an arrow to point to
the active state (which is displayed in capital letters). By default,
logging is enabled.
•
<3> Key -
Key <3> is used to enable/disable zone coding.
Pressing this key causes an arrow to point to the active state. By
default, zone coding is enabled.
•
<4> Key -
Key <4> is used to enable/disable the silent Walk
Test™. Pressing this key causes an arrow to point to the active
state (which is displayed in capital letters). By default, the silent
Walk Test™ is enabled.
Continued on next page
Walk Test™ PROCEDURES
Walk Test™ PROCEDURES,
Continued
How to Enter Walk
Test Mode
Содержание 4100U-S1
Страница 2: ......
Страница 10: ...viii...
Страница 18: ...1 8...
Страница 36: ......
Страница 46: ......
Страница 52: ......
Страница 64: ......
Страница 78: ......
Страница 82: ...11 4...