When the first alarm condition is detected by the 4100U-S1, the panel does the following to
indicate the presence of the alarm.
•
Red Fire Alarm and common Zone Alarm LED indicators flash
•
Red Zone Alarm LED flashes on the display module showing the affected zone.
•
Sounder (buzzer) pulses
•
Emergency Warning System (EWS) and External bell activate
•
Alphanumeric display on the operator interface shows the location and type (smoke, call
point, etc.) of the point in the alarm condition. An example is shown in Figure 2-1.
•
Any programmed outputs, including the Brigade connection, operate.
Figure 2-1. Alphanumeric Display Showing Typical Alarm
The first step in managing an alarm condition is to
acknowledge
the alarm. Acknowledging
an alarm does two important things:
•
It records the time and date at which you observed the presence of the alarm and stores
that information in the system’s historical log.
•
If multiple alarms are present, the system displays specific data for the next alarm when
you press the <FIRE ALARM ACK> key.
Acknowledging Alarms
What the System
Does When an
Alarm Occurs
Overview –
Acknowledging
Alarms