Master Controller (CPU) 

 

 

The 4010ES Master Controller includes dedicated 
2GB compact flash Mass Storage memory for on-site 
system information storage and convenient Ethernet 
service port access 

 

Convenient front panel accessed Ethernet port for 
quick and easy 

download

 of site-specific 

programming 

 

AND

, firmware enhancements are made via software 

downloads to the on-board flash memory 

 

Every downloaded job is automatically stored to 
Compact flash without overwriting earlier versions 
providing a means for recovering previous 
configurations 

 

Downtime is reduced because the system stays 
running during download 

 

Modifications can be 

uploaded

 as well as 

downloaded for greater service flexibility 

 

Mass Storage allows job specific files to be stored in 
the control panel such as test and inspection reports, 
record drawings, specifications, and more... 

 

Ethernet connectivity options include Building 
Network Interface Module (BNIC) and SafeLINC 
Internet Interface 

 

RUI (Remote Unit Interface) communications port 
supports either Class B or Class A operation for 
remote annunciation equipment 

 

Basic Panel Description 

 

4010ES panels with ESS include:  

 

An Operator Interface, Master Controller with 2 GB 
Compact Flash, IDNet 2 dual loop communications 
that provides Class B or Class A operation for up to 
250 addressable IDNet points, with dual short circuit 
isolating loop outputs, and 6 A Enhanced System 
Supply (ESS) 

 

RUI Class B or Class A communications port for 
remote annunciation devices 

 

Support for up to 20 internal and external card 
addresses 

 

Other standard features may be provided depending 
on model (see model selection below for additional 
details on specific models) 

 

Cabinet and door  

6 A Enhanced System Supply details: 

 

Two, 3 A Class B IDNAC SLCs for up to 254 
addressable notification appliances; Class A 
operation is available using the 4010-9930 Dual 
Class A IDNAC Isolator (DCAI) module 

 

Up to 2 A of auxiliary power 

 

110 Ah (UL)/50 Ah (ULC) battery charger (33 Ah 
maximum in the control panel cabinet) 

 

Low Battery Voltage Cutout is selectable when 

required (required for ULC listing applications) 

 

2 A for Regulated 24 DC operation; 1 programmable 
auxiliary relay rated for 2 A @ 32 VDC 

 

 

 
 
 
 

 

S4010-0011-5  11/2015

Model 

Panel 
Color 

Language 

& Voltage 

Listings  Features 

Supv. 

Current 

Alarm 

Current 

Available 

Option 
Blocks 

(see notes below) 

4010-9601 Red 

English 

120 VAC 

UL, 

CSFM, 

FM 

Basic 1- Bay Panel

 with 2x40 LCD 

Operator Interface, 6 A ESS/battery 
charger, (1) Two-loop Isolated IDNet 2 
Communications Channel, Class A or 
Class B, with support for up to 250 
addressable IDNet points; and two, 3 A, 
Class B, IDNAC SLCs with support for 
254 addressable notification appliances 

256 mA  390 mA 

4“x5” 

blocks 

4010-9602(BA)* Platinum 

4010-9603 Red 

English 

120 VAC 

UL, ULC, 

CSFM, 

FM 

Same features as above with 48 LED 
annunciation; alarm current includes 24 
annunciator LEDs activated 

276 mA  455 mA 

4010-9604 Platinum 

* BA model is assembled in the USA. 

Current Notes: 

1.  Basic panel current does not subtract from the 6 A output rating. 
2.  Supervisory and alarm current specifications are for determining battery standby requirements.  
3.  Current specifications include an active RUI channel.  
4.  IDNet channel device current is not included, refer to page 7 for details. 
5.  IDNAC channel notification appliance current is not included, calculate separately per connected devices. 

 Basic Panel Model Selection 

Содержание 4010-9601

Страница 1: ...either Class B or Class A operation 48 LED panel mount annunciation provides 40 Red and 8 Yellow pluggable LEDs select models meets ULC requirements optional LED kits are available to change individual LED color to Green or Blue to meet specific site requirements Optional ESS mounted modules door mounted modules and other options include City Connect with or without disconnect switches Alarm Relay...

Страница 2: ...of the 4010ES ESS There are 3 available 4 x 5 blocks for mounting 4010ES hardware options Other 4010ES Options The 4010ES City Connect module or the optional Alarm Relay module mount directly to the ESS These options are mutually exclusive Network Media modules mount directly to the 4010ES Network Interface Card The TrueInsight Remote Gateway mounts on the back side of the 4010ES User Interface Pa...

Страница 3: ... point category and point selection alphabet characters are not used at this time ADDITIONAL FUNCTION KEYS Event Time Request More Information Request Lamp Test Elevator Bypass City Disconnect Ground Fault Waterflow West Waterflow East Custom label insert LCD NAVIGATION CONTROL Menu selection Vertical and Horizontal position selection buttons 2 X 40 LCD READOUT LCD is backlighted during normal con...

Страница 4: ...details TrueAlarm heat sensors can be selected for fixed temperature detection with or without rate of rise detection Utility temperature sensing is also available typically to provide freeze warnings or alert to HVAC system problems Readings can selected as either Fahrenheit or Celsius TrueSense Early Fire Detection Multi sensor 4098 9754 provides photoelectric and heat sensor data using a single...

Страница 5: ...by appliances on the notification appliance circuit NAC making it much more difficult and costly to locate and correct the source of a problem Using the TrueAlert magnet test allows each appliance to individually identify its candela setting and address and to briefly operate if desired and using the TrueAlert ES Appliance Self Test feature provides detailed performance verification per appliance ...

Страница 6: ...epending on model see model selection below for additional details on specific models Cabinet and door 6 A Enhanced System Supply details Two 3 A Class B IDNAC SLCs for up to 254 addressable notification appliances Class A operation is available using the 4010 9930 Dual Class A IDNAC Isolator DCAI module Up to 2 A of auxiliary power 110 Ah UL 50 Ah ULC battery charger 33 Ah maximum in the control ...

Страница 7: ...from the list below 2 Vertical Blocks NA NA 4010 9922 Modular Network Interface Card requires two media modules see below 2 Vertical Blocks 30 mA 30 mA 4010 9818 Network Media Card Wired N A mounts to 4010 9922 55 mA 55 mA 4010 9819 Network Media Card Fiber Optic 25 mA 25 mA 4010 9914 Building Network Interface Card 2 Vertical Blocks 236 mA 236 mA 4010 9923 SafeLINC Internet Interface 2 Vertical B...

Страница 8: ...representative for more details LED Kits LEDs are pluggable use to change color for local application requirements Model Description 4100 9843 8 Yellow LED Kit 4100 9844 8 Green LED Kit 4100 9845 8 Red LED Kit 4100 9855 8 Blue LED Kit End User Programming Tools Model Description 4100 8802 End User Programming Unit Software 4100 0292 Custom Label Editing USB Dongle 4100 0295 Port Vectoring Setup an...

Страница 9: ...iator English 1 4606 9102CF 4010ES RUI LCD Annunciator French 1 for Canada 4602 9101 Status Command Unit SCU LED Annunciator 1 4602 9102 Remote Command Unit RCU LED Annunciator w control 1 4602 9150 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7101 Graphic I O RCU SCU Assembly for custom annunciator panels 1 4602 7001 RCU for cabinet mount 1 4602 6001 SCU for cabinet mount 1 4...

Страница 10: ...ence Installation Instructions 579 1150 Operating Instructions 579 969 Subject Data Sheet Subject Data Sheet 4010ES Agent Release Applications and Accessories S4010 0005 Network Communications S4100 0056 Agent Release Accessories S2080 0010 Multi Signal Fiber Optics S4100 0049 Building Network Interface S4100 0061 4602 Series SCU RCU S4602 0001 SafeLINC Internet Interface S4100 0062 PC Annunciator...

Отзывы: