Input (push-pull)
Use this setup to switch an input with a push-pull output. The push-pull
output can be regulated by an external system. This allows you to connect
an external system to the WaveNet.
+3.3 V
GND
OUT
GND
DI 3
DI 1
DI 2
Signal
transmitter
1. Connect the ground potentials of the signal transmitter and the router
node.
2. Connect the push-pull output of the signal transmitter to one of the di-
gital inputs DI1, DI2 or DI3.
IMPORTANT
Voltage ranges of the digital inputs
The push-pull output can work with unsuitable voltages. For the signal to
be reliably recognized as HIGH and LOW, it must be above or below the
reference voltages, depending on the signal level. The maximum output
voltage of the push-pull output must not exceed 3.3 V
DC
.
1. Do not use push-pull outputs whose voltage values for HIGH and LOW
do not match the equivalent voltages of RouterNode 2.
2. Do not use push-pull outputs whose maximum output voltage exceeds
3.3 V
DC
.
Comparison voltages (RN and RN2)
<0,9 V
DC
LOW (no signal)
WaveNet
(Manual)
5. WaveNet Manager