81
ENG
2. Scena connections
2.1 General connections
General observations
· Installation on the communication part must be done in
series
.
· Maximum
16 devices
with console’s own power supply (depending on the wiring distance).
No. of modules
Maximum distance from the last module
to the central console
1
550
5
115
10
55
16
33
· If connecting more devices, add an external source (Ref. 8999901-039). With additions, a maximum of 256
devices can be reached per console.
No. of modules
Maximum distance from the last module
to the central console
1
550
5
115
10
55
20
29
30
19
48
12
· A device can be: LightKeypad touch button box, 1-10V, electronic transformer Regulator Module, Electronic
Switch-Type Circuit Breaker, Blind control module, Digital signal converter, Analog signal converter, DMX-DALI
converter, DMX-PWM converter.
· Connection to the
GND grid
is vital. If the grid is not connected, noise can appear, affecting the installation’s
communications, causing it to function poorly.
· On the last element of the system a
120Ω end of line resistor
must be connected (included in the console
package).
Содержание Scena
Страница 1: ...MANUAL Y GU A DE INSTALACI N SCENA MANUAL AND INSTALLATION GUIDE...
Страница 4: ...4 CAST...
Страница 17: ...17 CAST 2 2 6 Modulo Regulador 0 10V 2 2 7 Modulo control de Persianas...
Страница 60: ...60 CAST 2 Conexionado tipo...
Страница 70: ...70 CAST MANUAL AND INSTALLATION GUIDE...
Страница 73: ...73 ENG...
Страница 86: ...86 ENG 2 2 6 0 10V Regulator Module 2 2 7 Blind control module...
Страница 129: ...129 ENG 2 Standard Connection...