116
ENG
Pantalla General
Pantalla Avanzada
3. Channels
We need to have created an
analog sensor for the
console
to relate the analog sensor with a channel.
The analog signal converter device has
2 inputs
and therefore
these two inputs will appear in the left zone. We select the one
we require depending on the installation.
To configure the CLC we have general and advanced mode.
Below we see the editable items in each case:
In the
General screen
we can check the sensor’s capture
and its status.
In the
Advanced screen
, we can modify certain of the
sensor’s values.
We can configure the set point in
Luxes
that will govern the channels connected to the CLC.
EQ Max and EQ Min
is the sensor’s lighting range. To do this, we need to consult its technical characteristics.
In this case we use the SIMON light sensor
Ref. 9000570-039
. The latter’s range is (0-1000 Lux) and output
0-10V.
EQ Max
: Maximum luminosity range.
EQ Min
: Minimum luminosity range.
Real Max Value
: Fixes the maximum value of the sensor’s output, in this case 10V.