User manual for - INDICATOR SWE-73-T
7.3.1.
“inPt” menu
This menu presets the measurement input:
“
tYPE
"
- type of the input / sensor. This parameter can be set to values:
”
Pt 1
”
- Pt-100 input,
”
Pt 5
”
- Pt-500 input,
”
Pt10
”
- Pt-1000 input.
”FiLt”
- this parameter sets filtration rate. It can be set to values from 0 (no filtration ) to 5
(strongest filtration – time window about 2 sec).
“toFS”
- offset (expressed in 0.1°C, range ± 9.9°C.). This parameter allows shifting of
measurement scale, and express value added to calculated (measured) result.
7.3.2.
”bri”
parameter
This parameter allows user to set bright of the LED display, bright can be set to
conventional values from 1 to 8.
7.3.3.
”HOLd” menu
This menu contains parameters connected with peak detection function. See also full
description of the peak detection function in paragraph:
DETECTION OF THE PEAK VALUES
“modE”
- the type of detected changes of the input signal, can be set to values:
”norm”
- peaks
, peak and next drop of the input signal of value equal at least
“PEA”
,
”inv”
- drops, drop and next peak of the input signal of value equal at least
“PEA”
,
“PEA”
- minimal detected signal change classified as peak or drop (see Figure 6.1)
“timE”
- maximum time of displaying of the peak (drop) value, can be set from 0.0 to 19.9
sec, with 0.1 sec. resolution. If „
HdiS
”=”
HOLD
” then setting parameter
"timE"
=
0.0
causes holding peak value until
[ESC]
button is pressed.
If „
HdiS
”=”
rEAL
” then
value
"timE"
=
0.0
means no holding.
“HdiS”
- type of displayed values:
”rEAL”
- current value is displayed,
”HOLd”
- peak (drop) value is displayed,
16