37
EN
7.6
Gas conversion
UNIQA REVOLUTION 25
models can be transformed from oper-
ating with G20 (methane) to G31 (LPG), by installing the “Nozzle
kit for G31” code 8059250, to be ordered separately from the
boiler, , also modifying
“PAR 03”
.
m
CAUTION
The maintenance interventions described must ONLY
be carried out the professionally qualified personnel.
a
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
OFF
Fig. 43
7.6.1
Preliminary operations
To carry out the conversion:
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
1
2
Fig. 44
– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
3
a
b
5
4
Fig. 45
– unscrew the screws (6) and remove the panel (7) carefully
7
6
Fig. 46