30
EN
– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
3
a
b
5
4
Fig. 30
– insert the connection wires into the cable gland (6) and the
opening (7) on the control panel
7
6
Fig. 31
– bring the control panel (4) to the original position and secure
it with the screws (3) which were removed previously
– connect the component wires to the terminal board (8) follow-
ing the indications provided on the data plate (9).
3
4
8
9
SE
TA
SIA
6
5
4
3
2
1
Fig. 32
m
CAUTION
It is compulsory:
– to use an omnipolar cut-off switch, disconnect
switch, in compliance with EN standards (contact
opening of at least 3 mm)
– if the power cable is to be replaced, that ONLY a spe-
cial cable is used with a factory produced re-wired
connector, ordered as a spare part and connected by
a professionally qualified person
– to connect the earth wire to an effective earthing
system (*)
– that before any intervention on the boiler, the mains
power is disconnected by setting the main system
switch to "OFF".
(*) The manufacturer is not responsible for any damage
caused by failure to earth the appliance or failure to ob-
serve the information provided in the wiring diagrams.
d
IT IS FORBIDDEN
To use water pipes for earthing the appliance.
6.12.1 External temperature sensor
The boiler is prearranged for connection to an external air tem-
perature sensor and can operate with a sliding temperature.
This means that the delivery temperature sent to the boiler can
vary on the basis of the external temperature depending on the
climatic curve selected from those shown in the diagram (Fig.
33).
When fitting the sensor on the outside of the building, follow
the instructions provided on the packaging of the product itself.
Climatic curve
Delivery temperature
20
15
10
5
0
80
90
70
60
50
40
30
20
°C
°C
K=9
K=7
K=8
K=5
K=6
K=3
K=4
K=2
K=1
External temperature
Fig. 33
m
CAUTION
If there is an external sensor, in order to select the op-
timal climatic curve for the system and therefore the
delivery temperature based on the external temper-
ature:
– press the button
t
for 1 second
– press buttons
>
or
<
until the required curve K has
been selected (within the range
K=0.0 - K=9.0
).