66
Installation is permanent and must exclu-
sively be performed by specialised and
qualified per sonnel, following all the
instructions and provisions included in
this manual. Current regulations must also
be met.
2.1
SUPPLY
“DEWY EQUIPE 60-120 BOX/P60-P120
BOX”
heat modules, inter-connectible by
flange, are supplied with an external pre-
painted zinc-coated laminate case.
They are complete with supply/return
wat er manifold fast ening screws and
gaskets and sequence/cascade digestion
unit cod. 8096301 supplied with
“120-
180-240 BOX/P120 BOX”
modules and
cod. 8096308 supplied with
“300-360
BOX”
modules.
Available separately:
– Safety kit to requested according to
module fixture positions:
code 8101511 for right-hand fixtures
code 8101510 for left-hand fixtures.
– Additional safety valve kit code 8103825
for modules
“300-360 BOX”
– Hydraulic separator kit:
code 8101550 for modules
“60-120-
180-240 BOX/P60-P120 BOX”
code 8101551 for modules
“300-360
BOX”
– Single box (size: 630 x 640 x 1600) for
hydraulic separator/safety kit, code
8101517 (figure 4)
– Double box (size: 1100 x 640 x 1600) for
hydraulic separator/safety kit and distri-
butors, code 8101518
– Polypropylene exhaust manifold kit for
indoor installation (purposely treated to
resist weathering when installed out-
doors):
code 8102510 for
“60-P60 BOX”
modu-
le
code 8102511 for
“120-P120 BOX”
module
code 8102512 for
“180 BOX”
module
code 8102513 for
“240 BOX”
module
code 8102514 for
“300 BOX”
module
code 8102515 for
“360 BOX”
module
– Exhaust terminal code 8089530 for out-
door installations.
To electrically connect the modules and to
assemble the exhaust for indoor or outdoor
installations, see points 2.6, 2.7 and 2.10 in
this manual.
2.2
INSTALLATION
2.2.1 Indoors
“DEWY EQUIPE 60-120-180-240-300-
360 BOX/P60-P120 BOX”
heat modules
can be installed in boiler rooms whose size
and requirements meet current regula-
tions. Furthermore, vents, with surface
areas at least 3.000 sq. cm or 5.000 sq.
cm for gas with density over 0.8, must be
installed in the outer walls for room ventila-
tion.
2.2.2
Outdoors
“DEWY EQUIPE 60-120-180-240-300-
360 BOX/P60-P120 BOX”
heat modules
can also be installed outdoors with the spe-
cif ic exhaus t f or single module cod.
8089530.
2.3
SYSTEM CONNECTIONS
To protect the heat system from damaging
corrosion, incrustation or deposits, after
installation it is extremely important to
clean the system using suitable products
such as, for example,
Sentinel X300 (new
systems), X400 and X800 (old systems)
or Fernox Cleaner F3
. Complete instruc-
tions are provided with the products but,
for further information, you may directly
contact SENTINEL PERFORMANCE SOLU-
TIONS LTD or FERNOX COOKSON ELECTRO-
NICS. For long-term protection agains cor-
rosion and deposits, the use of inhibitors
2
INSTALLATION
Fig. 4
45
1
600
695
355
630
640
403
44
0
81
0
355
47
0
“300-360 BOX”
“60
÷
240 BOX”
“P60-P120 BOX”