Installing a Rack
007-4566-001
9
3. Check the voltage between socket 1 (line) and the ground socket. The meter should
read between 200 and 240 VAC.
4. Check the voltage between socket 2 (neutral) and the ground socket. The meter
should read approximately 0 VAC.
5. Check the voltage between the ground socket and an earth-ground location. The
meter should read 0 VAC.
6. Change the voltmeter to a low-resistance setting.
7. Measure between the ground socket and an appropriate earth-ground location and
ensure that resistance is less than 1 ohm.
8. Repeat steps 1 through 7 for any additional single-phase power receptacles.
Caution:
If a voltage reading is incorrect, or if the resistance measured in step 7 is more
than 1 ohm, contact a site-approved electrician. Do not proceed with the installation.
Figure 1-2
32-amp Single-phase Power Plug for International Sites
!
Power cord
connector
Socket 1
(line)
Ground socket
Socket 2
(neutral)
Receptacle
Pin 1 (line)
Pin 2 (neutral)
Ground pin
Содержание Origin 350
Страница 1: ...SGI Origin 350 Server System User s Guide 007 4566 001 ...
Страница 3: ...007 4566 001 iii Record of Revision Version Description 001 June 2003 Original publication ...
Страница 4: ......
Страница 16: ......
Страница 26: ......
Страница 41: ...Installing a Rack 007 4566 001 15 Figure 1 5 Removing a Short Rack from the Shipping Crate Peg ...
Страница 50: ...24 007 4566 001 1 Installation and Operation Figure 1 11 Location of Table mounting Feet ...
Страница 90: ......
Страница 93: ...Physical Features 007 4566 001 67 Figure 2 1 Example of SGI Origin 350 Server Systems 17U rack 39U rack ...
Страница 132: ...106 007 4566 001 2 System Overview Figure 2 27 Front Views of Short and Tall Racks 17U rack 39U rack ...
Страница 158: ......
Страница 180: ......
Страница 204: ...178 007 4566 001 6 Installing and Removing Customer replaceable Units Figure 6 19 Installing a Disk Drive B A D C ...
Страница 206: ...180 007 4566 001 6 Installing and Removing Customer replaceable Units Figure 6 20 Removing a Disk Drive C A B D ...
Страница 211: ...Power Supplies 007 4566 001 185 Figure 6 23 Installing the power supply Bezel door Screen cover Ribbon cable D C A B ...
Страница 228: ......
Страница 262: ......
Страница 274: ......