Hardware Installation
151165
4-7
4.7
Optional Accessories Installation
This section describes how to install the optional accessories compatible with the SK-2224
control panel.
4.7.1
Installing the Serial Driver Board (Model SK-2884)
The SK-2884 is required if the installation uses any SK-2224 expansion devices such as
Model SK-2880 (I/O Module), Model SK-2866 (LED Annunciator), or Model SK-2104
(DACT). The SK-2884 interfaces all the expansion devices to the SK-2224 control panel.
Note: The SK-2104 Dialer board is not available for control panels that have the releasing (cross alarming)
feature.
Follow these steps to install the SK-2884 Serial Driver Board:
1. Unplug the AC power connector from the SK-2224 control panel. See Figure 4-1.
2. Unplug the battery connector from the SK-2224 control panel. See Figure 4-2.
3. Plug the SK-2884 Serial board onto the SK-2224 control panel by aligning the 4-pin con-
nector and the stand-offs with their respective receptors. See Figure 4-8.
Figure 4-8 Model SK-2884 Connector and Stand-off alignment
4. Reconnect the AC power connector to the control panel. See Figure 4-1.
5. Reconnect the battery connector to the control panel. See Figure 4-2.
Содержание SK-2224
Страница 1: ...Fire Control Panel Part Number 151051F 02 02 SK 2224 Installation and Operation Manual ...
Страница 5: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 1 2 151165 ...
Страница 7: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 2 2 151165 ...
Страница 17: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 3 10 151165 ...
Страница 39: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 6 4 151165 ...
Страница 59: ...Cut Along the Dotted Line ...