![SILENT KNIGHT SK-2224 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/silent-knight/sk-2224/sk-2224_installation-and-operation-manual_1271109014.webp)
Before You Begin Installing
151165
3-7
3.8
Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can cause false alarms
or interfere with control panel operation in other ways.
To avoid induced noise, follow these guidelines:
•
Isolate input wiring from high current output and power wiring. Do not pull one multicon-
ductor cable for the entire panel. Instead, separate the wiring as follows:
High current input/output:
AC power, speaker, and notification appliance wiring
Low current input/output:
Annunciator and initiating circuit wiring
Audio input/output:
Telephone wiring
•
Do not pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield
to circuit ground at the panel. You must route high and low voltages separately.
•
Route the wiring within the cabinet around the perimeter of the cabinet. It should not cross
the printed circuit board where it could induce noise into the sensitive microelectronics or
pick up unwanted RF noise from the high speed circuits. See Figure 3-4 for an example.
•
High frequency noise, such as that produced by the inductive reactance of a speaker or
bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it
around a ferrite toroid.
Figure 3-4 Wire Routing Example
Important!
Do not run 120 VAC line voltage in fire alarm raceways.
Содержание SK-2224
Страница 1: ...Fire Control Panel Part Number 151051F 02 02 SK 2224 Installation and Operation Manual ...
Страница 5: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 1 2 151165 ...
Страница 7: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 2 2 151165 ...
Страница 17: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 3 10 151165 ...
Страница 39: ...Model SK 2224 Fire Alarm Control Panel Installation Operation Manual 6 4 151165 ...
Страница 59: ...Cut Along the Dotted Line ...