Model SK-2224 Fire Alarm Control Panel Installation/Operation Manual
4-2
151165
4.2
Battery Connection
The SK-2224 battery charge capacity is 7.0 AH. Use two 12V batteries of the same AH rating.
Determine the correct AH rating as per your current load calculation (see Table 3-6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
Note: The SK-2224 cabinet supports two 7.0 AH batteries.
Figure 4-2 Battery Connection
Battery jumper (P/N140694)
shipped with the control panel.