Installation
151059
3-9
3.7.3
Programmable Remote Alert Output
1. Plug the Relay wiring harness onto the connector on the back of the 9500. (See Figure 3-
8.)
Note: The remote alert output is a form C relay with a normally open or a normally closed wire.
Figure 3-8 9500 Remote Alert Output/External Backup Battery Connection
2. Connect the white wire to common.
3. Use the Yellow wire for a normally closed circuit
Or
Use the Brown wire for a normally open circuit.
3.8
AC Power Cord Connection
3.8.1
Using Standard Power Cord
1. Connect the appropriate end of the power cord into its receptacle on the back of the 9500.
2. Plug the three-pronged end of the power cord into a 120 VAC 60 Hz outlet (three-prong
type only). The outlet should be unswitched, so that power remains on 24 hours a day. The
outlet must also be earth grounded. Follow the directions in Section 3.8.4 if you need to
measure for proper earth grounding.