Section 3
Installation
This section contains information necessary to install a 9500 Central Station Receiver.
3.1
Environmental Specifications
•
Intended for indoor use in dry locations only
•
Non-corrosive environment
•
Temperature range: 32º to 120º F
•
Humidity:10%-93% at 30°C (86°F) noncondensing
3.2
Electrical Specifications
IMPORTANT
:
Do not connect power to the system until you have read these instructions carefully.
Line Voltage:
120VAC ± 10%
60Hz, 100VA
240VAC ± 10%
50Hz, 100VA
Fuse:
2.5A Slow Blow
Backup Battery Connection:
Note:
A 12 VDC battery
does not provide standby
time required by UL and
NFPA standards. A UPS
(listed for fire protective
signaling use) must be
utilized when standby power
is required. See 5.4.4 for
details on backup battery
configuration.
Input
12 VDC Nominal
3 Amp Max.
Output
13.65 VDC
1 Amp charging current
Auxiliary Relay (Programmable):
2.5 Amp @ 24 VAC/VDC(Inductive), 0 Hz
5 Amp @ 24 VAC/VDC(Resistive), 0 Hz