Siko MA10/4 Скачать руководство пользователя страница 21

 

 

MA10/4-SW02

 

Date: 06.05.2014 

Page 21 of 23 

Art.No. 87185 

Mod. status 422/13 

Long telegram from address 7 (07h); read out position value (16h); value 203h = 515 dec (03 02 
00h); check byte (10h). 

10 

Application examples 

10.1 

Example of Modulo display mode 

The position of the motor shaft on a motor is to be recorded (0° ... 359°) with a resolution of 
0.1°. An incremental encoder with 1000 pulses per revolution is attached to the motor shaft. 
Thus, the display should count from 0.0 ... 359.9 and then jump back to 0.0. 

Parameter programming: 

Parameter 

Input 

Explanation 

WINK: 

modulo 

Set modulo display mode. 

DEC: 

0.0 

Enter positions after the comma. 

MOD.W: 

360.0 

Enter modulo value. 

DRP: 

360.0 

Enter display after one revolution. 

DIVISOR: 

Enter display divisor. 

INCR: 

1000 

Enter pulses per revolution. 

10.2 

Example: Mitre-box saw (Display mode 0-90-0) 

An MA10/4 as an angle display is tho be installed on a mitre-box saw. While the saw blade is 
swinging, the measured value shall decrease from 90° in the direction of 0° on both sides. An 
incremental encoder with 100 pulses per revolution is available, the resolution shall be 1°. 

Parameter programming: 

Parameter 

Input 

Explanation 

WINK: 

0-90-0 

Set display mode 0-90-0. 

DEC: 

0. 

Enter positions after the comma. 

DRP: 

360 

Enter display after one revolution. 

DIVISOR: 

Enter display divisor. 

INCR: 

100 

Enter pulses per revolution. 

10.3 

MA10/4 combined with an MSK magnetic sensor and the MR magnetic ring 

If an MSK magnetic sensor with an MR magnetic ring is used instead of an incremental 
encoder, then the "encoder pulses per revolution" of the magnetic ring must be determined in 
order to enable parameterization of the magnetic display. The "encoder pulses per revolution" is 
calculated from the pose number of the magnetic ring and the scaling factor of the MSK sensor 
according ro the following formula: 

Encoder pulses per revolution = number of poles of magnetic ring x scaling factor of sensor 

Содержание MA10/4

Страница 1: ...User manual Electronic display MA10 4 Software SW02...

Страница 2: ...teration of reference offset value or calibration offset value 12 6 4 Direct input of limiting value 12 7 0 90 0 Angle display 13 7 1 Input of limit with switching output option 13 8 Referencing Calib...

Страница 3: ...10 4 SW02 can be used for measuring angles in three ranges of resolution 1 0 1 0 01 After reaching the respective maximum value e g 359 programmable modulo value the display jumps to 0 With opposite s...

Страница 4: ...he input mode 1 2 3 4 5 6 7 8 9 10 11 12 Digit R 1 5 9 9 Angle value Digit Symbol Description 1 R Incremental measure is active 3 Upper limiting value exceeded only for output circuit option 3 Lower l...

Страница 5: ...y until the end of the parameter list is reached To scroll parameter information Use key Input of numerical values For numerical values the smallest decade flashes first The numerical value of the fla...

Страница 6: ...fter 1 revolution Value by which the display increases decreases after 1 revolution of the encoder If DPR 0 quadruple evaluation of the encoder signal will take place automatically DIVISOR 1 10 100 10...

Страница 7: ...n or offset measure for instance RESET off on del 1s del 3s Reset via keyboard enable off reset function off on reset function enabled del 1s reset function enabled press key for at least 1 sec del 3s...

Страница 8: ...value Menu item will be displayed only if SCHALT is programmed for BAUD Possibility of input modification of the upper and lower limiting values in the input mode off Modification of limiting values d...

Страница 9: ...al encoder bit number DPR 0 59999 Display after 1 revolution Menu item will be displayed only if multi is programmed for E TYP Value by which the display increases decreases after 1 revolution of the...

Страница 10: ...TPUT gray bin Output code gray Encoder s data in Gray code bin Encoder s data in binary code TIMEOUT off on Time out function off Cable break recognition off on Cable break recognition off P KEY 3s 5s...

Страница 11: ...med to on del 1s or del 3s but unit must not be left in programming mode see chapter 4 To leave programming mode For modulo display mode Press key to set the display to reference calibration offset va...

Страница 12: ...once again The display then shows the offset value which can be changed via the two arrow keys By pressing the key the value is saved and directly taken over in the display Finishing direct input of r...

Страница 13: ...Input of limit with switching output option When entering the limits that are in the quadrant 1 please note that they cannot be entered directly as with quadrant 0 but must be calculated according to...

Страница 14: ...ogrammed to 0 8 2 Automatic referencing Only incremental Automatic referencing is always made via a reference point transmitter which is automatically approached at a defined position reference value...

Страница 15: ...ving spindle if you untighten the clamping ring or coupling You can now search the index signal of the encoder voltage change by using for example a voltmeter and carry out the adjustment of the refer...

Страница 16: ...dditional parameters The MA10 4 transmits its answer with automatic Carriage Return CR Input Lower and upper cases are accepted ASCII Output All response telegrams are completed with a CR hex 13 excep...

Страница 17: ...ber of pulses y 2 positions after the comma y 4 encoder bits SSI only y 5 singleturn bits SSI only y 6 modulo value Iabc 4 2 Release frontal keys a reset via keyboard 0 off 1 on 2 1 sec delay 3 3 secs...

Страница 18: ...1 3 xyz Binary position value xyz 3 bytes in two s complement MSB LSB Xy 2 2 Enter unit of measure y number y 0 no y 1 angle degree Yx 2 2 Enter display divisor incremental and SSI only x number x 0...

Страница 19: ...ted command 0x32 0x33 R This command can be broadcasted Hex TX RX S P R Function 0x16 3 6 Read out position value 0x18 3 6 Read out reference calibration value 0x19 3 6 Read out offset value 0x1b 3 6...

Страница 20: ...6 6 S P Program index type only incremental see command 0x6c 0x72 3 6 Output configuration bits 0x73 6 6 S P Program configuration bits 0x7e 3 6 Send type of reference switch only incremental 0x7f 6 6...

Страница 21: ...tho be installed on a mitre box saw While the saw blade is swinging the measured value shall decrease from 90 in the direction of 0 on both sides An incremental encoder with 100 pulses per revolution...

Страница 22: ...l value store programmed to off Carry out reference calibration 12 Parameter list 12 1 Incremental version Display Selection value Default value Your own programming use 1 2 3 LANGUAGE deu eng deu WIN...

Страница 23: ...lo 0 90 0 modulo DEC 0 0 0 0 00 0 0 MOD W 0 59999 360 0 E TYP multi single multi FORMAT no Tree no S BITS 5 19 10 ENCOD BIT 5 25 22 DPR 0 59999 0000 0 DIVISOR 1 10 100 1000 1 DIRECTION i e i CAL 99999...

Отзывы: