S-DIAS ETHERCAT CONTROL MODULE
EC 121
02.07.2020
Page 61
Example for configuration file entries:
•
64 S-DIAS slaves are connected to the EC 121
•
In module slots 1 -32, S-DIAS slaves with the DeviceID = 1026 are connected
•
In module slots 33-64, S-DIAS slaves with the DeviceID = 1016 are connected
•
A firmware update should be run for the first 4 (1, 2, 3, 4) and the last 4 (61, 62,
63, 64) module slots.
The configuration could then appear as follows:
1026-2-INC-0x000000000000000F
1016-2-EXC-0x0FFFFFFFFFFFFFFF
The configurations are entered by line for the corresponding S-DIAS slave or target device.
If the parameters from the configuration file do not match the specification, the module is
not updated and a log entry is created. As soon as all updates are complete and there are
no more update files in the verified folder, the configuration file is deleted.
12.2 Providing Update Files
As previously mentioned in section 11.4, the EC 121 does not accept default update imag-
es. The update images must contain a special header and a signature. The header and
signature can only be added to the file by SIGMATEK.
For each update type (EC 121 Firmware, EC 121 FPGA, Slave Firmware,
Slave CPLD/FPGA), the corresponding update image must be requested
from and/or provided by SIGMATEK.