7.2.4 Status Register
The MDD 100 has a status register, read by
I-STATUS
. It is a 32-Bit variable that contains
all error and status information. The internal behavior of the drive to the different bits can be
set by
G-MASKE1
,
G-MASKE2
,
G-MASKW
and
G-MASKD
. According to the setting of the
different masks, the drive detects an error, warning or does not react at all. The different
bits have default values and also limitations on attribution to the masks.
Bit
Fault
Cause
Remedy
0
One mains phase
─ No 3-phase supply from the
mains
─ check fuses in the mains
─ check electrical supply
1
Mains fault
─ Drive system is enabled
without mains applied
─ check fuses in the mains
─ check electrical supply
─ Drive is enabled, before
DC
– link charged and vice versa
2
Not used
3
DC over voltage
─ internal regen resistor dama-
ged
─ replace module rack
4
DC under voltage
─ mains supply voltage too low
when drive is enabled
─ disable drive before the DC-link
voltage crosses the under voltage
threshold set by
G-VBUSM
5
Not used
6
Holding brake fault
─ No holding brake connected
with
M-BRAKE
= 1
─ Short circuit at the holding
brake output
─ Connect motor with holding brake
─ Check wiring of the holding brake
─ Set
M-BRAKE
= 0 if no brake is at
the motor
─ Check wiring of the holding brake
─ Check holding brake
7
Brake switch fault
─ No holding brake connected
with
M-BRAKE
= 1
─ Internal brake supply switch is
defect
─ Connect motor with holding brake
─ Set
M-BRAKE
= 0 if no brake is at
the motor
─ replace drive
8
Not used
9
Motor temperature
─ motor thermostat has
switched off
─ break in feedback cable or
connectors
─ check why the motor became
so hot (undersized, bad envi-
ronmental conditions)
─ check feedback cable and
connectors, replace it, if neces-
sary
Содержание MDD 111-1
Страница 4: ...MDP 102 1 Page 4 29 08 2019 1 1 Components of a servo system...
Страница 13: ...MDP 102 1 29 08 2019 Page 13 2 6 Nameplate...
Страница 14: ...MDP 102 1 Page 14 29 08 2019 2 7 Block Diagram and Concept Block diagram of the Power Supply Module...
Страница 27: ...MDP 102 1 29 08 2019 Page 27...
Страница 28: ...MDP 102 1 Page 28 29 08 2019 Connector layout of X1 X2 X3 X4 and X6...
Страница 30: ...MDP 102 1 Page 30 29 08 2019 The entire MDD System is grounded over the module carrier in the control cabinet...
Страница 48: ...MDP 102 1 Page 48 29 08 2019...
Страница 50: ...MDP 102 1 Page 50 29 08 2019...
Страница 84: ...MDP 102 1 Page 84 29 08 2019...