3.2 Important instructions for the Safety Function
•
All control components (switches, relays, PLC, etc.) and the control
cabinet must comply with the requirements of the ISO 13849. This in-
cludes:
–
Door
– switches, etc. with protection class IP54 as minimum
–
Control cabinet with protection class IP54 as minimum
•
For the 24 V supply use only PELV/SELV power supplies.
•
Use adequate insulated wire end sleeves
•
•
External source voltage at the inputs ENABLE_L and ENABLE_H has
to be excluded in the cabinet and outside. Make sure, that short cir-
cuits between single cables are excluded! See also EN ISO 13849.
•
All safety-relevant cables (e. g. control cable) has to be installed e. g.
in a cable duct, if pass outside the control cabinet
•
The connector pin X1 / 3 is marked as “reserved” and must not be
connected externally
Содержание MDD 111-1
Страница 4: ...MDP 102 1 Page 4 29 08 2019 1 1 Components of a servo system...
Страница 13: ...MDP 102 1 29 08 2019 Page 13 2 6 Nameplate...
Страница 14: ...MDP 102 1 Page 14 29 08 2019 2 7 Block Diagram and Concept Block diagram of the Power Supply Module...
Страница 27: ...MDP 102 1 29 08 2019 Page 27...
Страница 28: ...MDP 102 1 Page 28 29 08 2019 Connector layout of X1 X2 X3 X4 and X6...
Страница 30: ...MDP 102 1 Page 30 29 08 2019 The entire MDD System is grounded over the module carrier in the control cabinet...
Страница 48: ...MDP 102 1 Page 48 29 08 2019...
Страница 50: ...MDP 102 1 Page 50 29 08 2019...
Страница 84: ...MDP 102 1 Page 84 29 08 2019...