#15079 FRD-HD c/w REGULATOR
We recommend using an elbow fitting on the fuel inlet (1/8 npt female thread). When
priming this pump hold down the knob of the pressure regulator to prime the fuel lines
and take out the air then turn the dial to the lowest setting on the regulator and increase
pressure 1 increment at a time until the pump is just delivering a small amount of fuel as
the heater/stove only requires a very small amount .
Trouble Shooting
Check for air leak on supply side of pump, tighten fittings
Check for clogged fuel filter
Ensure adequate 12v power
Ensure the pump is installed as high as the valve of the heater/stove
Use 3/8" (9.52 mm) copper fuel line for the first 2-3 ft closest to the heater/stove.
Approved hose can be used for the remainder of the installation. DO NOT USE A
PRESSURIZED FUEL TANK.